Rockwell Automation Publication 2198-RM003A-EN-P - February 2020
65
Dimensions, Cables, and Wiring
Chapter 4
Figure 32 - Kinetix 5100 Drive Three-phase (200…230V) Grounded Power Configuration
(wye secondary)
Single-phase Power Wired to Single-phase Kinetix 5100 Drives
These examples illustrate grounded single-phase power that is wired to single-
phase Kinetix 5100 drives when phase-to-phase voltage is within drive
specifications.
Figure 33 - Kinetix 5100 Single-phase (200…230V) Grounded Power Configuration
L3
L2
L1
L3
L2
L1
E
L3
L2
L1
L3
L2
L1
2198-E
xxxx
-ERS
Servo Drives
L1C
L2C
Transformer (wye) Secondary
Mains AC Input
Power Connector
Bonded Cabinet Ground Bus
Ground Grid or Power
Distribution Ground
AC Line
Filter
Circuit
Protection
Feeder and branch short-circuit
protection is not illustrated.
M1
Contactor
Control AC Input
Power Connector
Circuit
Protection
ATTENTION:
For the 230V Kinetix 5100 drives to meet proper voltage creepage
and clearance requirements, each phase voltage to ground must be less than or
equal to 253V AC rms. This means that the power system must use center-
grounded wye secondary configuration for 230V AC mains.
L2
L1
L2
L1
L2
L1
L2
L1
E
L1C
L2C
Transformer Secondary
Bonded Cabinet Ground Bus
Ground Grid or Power
Distribution Ground
AC Line
Filter
200…230V AC
Output
Circuit
Protection
M1
Contactor
Circuit
Protection
Mains AC Input Power
Connector
Control AC Input Power
Connector
2198-E1004-ERS, 2198-E1007-ERS,
2198-E1015-ERS, and 2198-E1020-ERS
Drives with Single-phase Operation
Reducing the transformer output reduces motor speed. Feeder and branch short-circuit protection is not illustrated.