2

Rockwell Automation Publication 440R-IN088A-EN-P - July 2022

Minotaur MSR138DP, MSR138.1DP Monitoring Safety Relay Installation Instructions

Diagnostics

The solid-state status signal Y35 indicates the safety input state. The solid-state 
status output Y32 and the auxiliary (N.C.) output 41-42 signals the safety output 
state.

Safety Input

One safety device can be monitored per unit. According to the wiring inputs, 
cross-loop monitoring of the inputs is enabled or disabled. You can enable 
cross-loop monitoring for 2-channel safety inputs in 4-wire connection (S11-S12, 
S21-S22). Cross-loop monitoring is disabled for single-channel inputs, dual-channel 
inputs in 3-wire connection, and 24V DC signals. For external 24V DC signals, the 
negative pole must connect to S21.

Reset

Reset modes - The reset mode is configurable for automatic/manual start 
and manual monitored reset (MSR

xxx

RT). 

A valid start/reset can only operate if the feedback circuit (Y1-Y2) and the 
time-reset circuit (Y39-Y40) are closed. Feedback contacts (N.C.) of 
controlled actuators connect to Y1-Y2. Start/reset during the time lapse 
causes a fault state. To avoid a lockout condition by start/reset, the N.C. 
contacts (55-56) of the MSR138.1 safety relay connect in series with the 
feedback circuit Y1-Y2.

T - Automatic/manual start 

(a)

In Automatic/Manual Start mode, the reset circuit S33-S34 is not 
monitored against signal changes (no edge detection). The safety relay is 
active once the safety inputs and the reset circuit close. If the safety 
inputs and reset circuit concurrently close during power-up, the safety 
relay activates immediately.

R - Manual monitored reset 

(b)

In Manual Monitored Reset mode, a signal change of the reset circuit 
(S33-S34) is required and monitored. A reset fault occurs if the safety 
inputs remain open while the reset circuit is closed.

-

Positive edge:

The safety relay is active once the safety inputs close and then the 
reset circuit is closed.

-

Negative edge (440R-

xxxxx

M):

The safety relay is active once the safety inputs close and then the 
reset circuit closes and releases again. The circuit resets upon release 
of the Reset button.

For both methods, the MSR138/.1DP safety relay is suitable for the safety 
requirements according to EN/ISO 13849-1.

Installation group

Overvoltage category III, VDE 0110-1

Operating temperature

-5…+55 °C (23…131 °F)

Relative Humidity

90%

Enclosure protection

IP40 (NEMA 1)

Terminal protection

IP20

Wiring

Use copper that withstands 60/75 °C (140/167 °F)

Conductor size

0.2...2.5 mm

2

 (24…12 AWG)

Torque settings

Terminal screws: 0.6…0.8 N•m (5…7 lb•in)

Case material

Polyamide PA 6.6

Mounting

35 mm (1.38 in.) DIN rail in enclosure to a minimum of IP54

Weight

24V AC/DC: 350 g (0.77 lb)
115V AC or 230V AC: 490 g (1.08 lb)

Vibration

10…55 Hz, 0.35 mm (0.01 in.)

(1)

Operation time (day, hour)

(2)

Cycle time (hour, sec)

Max PLc: 1-CH 

(1)

; N.C.

(1)

1-CH = Single-channel

Max PLd: 2-CH 

(2)

; 3-wire connection

(2)

2-CH = Dual-channel

Max PLe: 2-CH 

(2)

; 24V DC signal

Max PLe: 2-CH 

(2)

; 4-wire connection, cross 

faults require fault reset

Table 1 - Technical Specifications  (Continued)

Attribute

Value

(a)

T = Jumper X1-X2, X3-X4

(b)

R = No jumper

MSR

xxx

T

MSR

xxx

T

440R-

xxxxx

M

MSR

xxx

R

MSR

xxx

R

440R-

xxxxx

M

MSR

xxx

R

440R-

xxxxx

M

Summary of Contents for Allen-Bradley Minotaur MSR138DP

Page 1: ...r manipulation can result in serious injuries Do not defeat tamper remove or bypass this unit ATTENTION If any malfunction or damage is present do not attempt to repair Replaced the unit before machine operation is allowed Do not dismantle the unit IMPORTANT The safety inputs of these products are described as normally closed N C that is with the guard closed the actuator in place where relevant a...

Page 2: ...lose If the safety inputs and reset circuit concurrently close during power up the safety relay activates immediately R Manual monitored reset b In Manual Monitored Reset mode a signal change of the reset circuit S33 S34 is required and monitored A reset fault occurs if the safety inputs remain open while the reset circuit is closed Positive edge The safety relay is active once the safety inputs c...

Page 3: ...21 S22 Safety input N C X1 X2 X3 X4 S33 S34 Link for auto reset Y1 Y2 Monitoring loop feedback Y39 Y40 Timer override 13 14 Safety output 1 N O 23 24 Safety output 2 N O 37 38 Timer output 1 N O 47 48 Timer output 2 N O 57 58 1 1 MSR 138DP Timer output 3 N O 55 56 2 2 MSR 138 1DP Timer output 3 N C PWR Status indicator illuminates green when the unit is powered flashing green if cross loop faults ...

Page 4: ... MSR138 1DP safety relay in safety circuits according to DIN EN 60204 1 VDE 0113 part 1 Safety requirements that are specified in Specifications on page 1 are maximum based on the operation mode and wiring Specifications are applicable only if the safety function is demanded at least once within 6 months All diagnostic tests are conducted at least before next demand The mission time TM for the pro...

Reviews: