Rockwell Automation Publication 2715P-UM001C-EN-P - March 2019
101
Troubleshooting
Chapter 7
Cannot Download
Application to Terminal
You are unable to download an application to the terminal.
Performance Is Slow
If the response time of the application is slow, for example screen changes or text
display changes, check for the following conditions:
• Application screens that contain too many elements
• A controller that is programmed for feedback can cause delays
• Slow network performance or noise can result in retries
Resistance to Chemicals
The outer surfaces of the terminal including the bezel, touch screen overlay, and
panel gasket are tested for chemical resistance. Some of the chemicals can cause
discoloration, but they do not interfere with the operation of the terminal.
Poor cable connections
Check the Ethernet cabling for the following:
• Make sure that cables are fully connected.
• Check for cable crimping.
• Check the Ethernet switch connections.
• Check the Uplink ports.
Invalid IP address of terminal
If DHCP is enabled, the terminal automatically acquires a valid
IP address from the network after startup. The TCP/IP protocol
automatically assigns 169.254.
xxx.xxx
when it fails to acquire
an IP address from the network. In general, an IP address that
begins with 169 does not support a network connection.
See
Configure the IP Address of the Terminal on page 48
Conflict Between IP addresses
If DHCP is not enabled and a static IP address is specified,
make sure that the IP address does not conflict with the
address of another device on the network.
See
Configure the IP Address of the Terminal on page 48
Table 28 - Ethernet Connection Issues (Continued)
Check for
Description
Table 29 - Unable to Download Project to Terminal
Check for
Description
Application downloads are disabled in Settings
screens
Verify that downloads are enabled. See
.
Download of project to correct HMI device
Check the following in the View Designer application:
• The project that is downloaded to the correct HMI device
• IP address of HMI device is correct
Ethernet connection
Make sure that an Ethernet cable is connected between the
computer and terminal.
Verify that the Ethernet port is configured properly. See
.
TIP
For more information on chemical resistance of the product, go to
http://www.rockwellautomation.com/knowledgebase
Knowledgebase for keywords ‘Chemical Resistance PanelView™ Plus’.
IMPORTANT
Do not operate the terminal in direct sunlight. Direct exposure to ultraviolet
light can discolor the touch screen.
Summary of Contents for Allen-Bradley PanelView 5510 Series
Page 6: ...6 Rockwell Automation Publication 2715P UM001C EN P March 2019 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 2715P UM001C EN P March 2019 Preface Notes...
Page 108: ...108 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Page 109: ...Rockwell Automation Publication 2715P UM001C EN P March 2019 109 Index Notes...
Page 110: ...110 Rockwell Automation Publication 2715P UM001C EN P March 2019 Index Notes...
Page 111: ......