Programming and Parameters
3-19
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
A058,
A061
Options
(Cont.)
18 “Above PF Ang”
•
Power Factor angle has exceeded the value set in
or
[Opto Outx Level].
•
Use A059 or A062 to set threshold.
19 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In
Loss] for desired action when input loss occurs.
20 “ParamControl”
Prior to FRN 4.01, this option enables the output to be
controlled over network communications by writing to
[Opto Outx Level]. (0 = Off, 1 = On.)
With FRN 4.01 and later:
Setting this option for A058 means the logic command word
bit 6 has full control of A059.
Setting this option for A059 means the logic command word
bit 7 has full control of A062.
See
Writing (06) Logic Command Data on page C-4
.
21 “NonRec Fault”
•
[Auto Rstrt Tries] is exceeded.
•
[Auto Rstrt Tries] in not enabled.
•
A Non-resettable fault has occurred.
22 “EM Brk Cntrl”
EM brake is energized. Program
[EM Brk Off Delay] and
[EM Brk On Delay] for desired action.
23 “Above Fcmd”
The current commanded frequency exceeds the value set in
24 “MsgControl”
With FRN 4.01 and later:
Enables the output to be controlled over the network
communications by writing to
or
[Opto Outx
Level]. (0 = Off, 1 = On.)
A059 [Opto Out1 Level]
Related Parameter(s):
,
A062 [Opto Out2 Level]
32 bit parameter.
Determines the on/off point for the opto outputs when
or
[Opto Outx Sel] is set to option 6,
7, 8, 10, 16, 17, 18 or 20.
With FRN 4.01 and later, when the value of A058 is set to 20, the logic command word bit 6 has full
control of A059 and when the value of A061 is set to 20, bit 7 has full control of A062.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
A058 & A061 Setting
A059 & A062 Min/Max
6
7
8
10
16
17
18
20
23
0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0/400 Hz