PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
3-50
Programming and Parameters
UTILITY
Di
agnostic
s
401
[Spd Select 1]
Indicates the state of the assigned digital input, [Digital Inx Sel], set to
18 “Speed Sel 2”. Refer to
Option Definitions for [Digital Inx Sel] on
for instructions on how to set digital input speed selects to
different speed references.
•
“0” = Digital input [Digital Inx Sel] set to 18 “Speed Sel 2” not
asserted
•
“1” = Digital input [Digital Inx Sel] set to 18 “Speed Sel 2” asserted
Note: By default, the state of this parameter is determined by digital
input 6.
Default:
Min/Max:
Read Only
0 / 1
400,
402
402
[Spd Select 2]
Indicates the state of the assigned digital input, [Digital Inx Sel], set to
19 “Speed Sel 3”. Refer to
Option Definitions for [Digital Inx Sel] on
for instructions on how to set digital input speed selects to
different speed references.
•
“0” = Digital input [Digital Inx Sel] set to 19 “Speed Sel 3” not
asserted
•
“1” = Digital input [Digital Inx Sel] set to 19 “Speed Sel 3” asserted
Note: By default, the state of this parameter is determined by digital
input 7.
Default:
Min/Max:
Read Only
0 / 1
400,
401
403
[Ramp Select 0]
Indicates the state of the assigned digital input, [Digital Inx Sel], set to
25 “Acc2 & Dec2” or 26 “Accel 2”.
•
“0” = Accel 1 ramp rate is selected
•
“1” = Accel 2 ramp rate is selected
Note: This parameter can be assigned to indicate the state of a digital
input.
Default:
Min/Max:
Read Only
0 / 1
404
404
[Ramp Select 1]
Indicates the state of the assigned digital input, [Digital Inx Sel], set to
25 “Acc2 & Dec2” or 27 “Decel 2”.
•
“0” = Decel 1 ramp rate is selected
•
“1” = Decel 2 ramp rate is selected
Note: This parameter can be assigned to indicate the state of a digital
input.
Default:
Min/Max:
Read Only
0 / 1
403
651
[Encoder State]
Indicates the connection status of the digital encoder or tachometer.
•
“0” = Fault
•
‘1” = OK
This parameter can be assigned to a digital output.
Default:
Min/Max:
Read Only
0 / 1
1188 [Accel Status]
Indicates the drive acceleration status.
•
“0” = Off - Drive not accelerating
•
“1” = “On” - Drive accelerating
Note: This parameter can be assigned to a digital output.
Default:
Min/Max:
Read Only
0 / 1
1189 [Decel Status]
Indicates the drive deceleration status.
•
“0” = “Off” - Drive not decelerating
•
“1” = “On” - Drive decelerating
Note: This parameter can be assigned to a digital output.
Default:
Min/Max:
Read Only
0 / 1
1190 [Fast Stop Status]
Indicates the drive fast stop status.
•
“0” = “Off” - Drive is not fast stopping
•
“1” = “On” - Drive is fast stopping
Default:
Min/Max:
Read Only
0 / 1
File
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
A
A
A
A
A
A
A
A