PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
Installation and Wiring
1-33
Table 1.L Control Circuit Board Jumper and DIP Switch Settings
ID
Jumper/
Switch
Function
Factory
Default
S0
For factory boot flashing only. Leave set to the factory setting.
Jumper Off
Jumper On
Firmware boot
Jumper Off
Normal function
S1
For factory boot flashing only. Leave set to the factory setting.
Jumper Off
Jumper On
Write firmware boot code
Jumper Off
Boot code on flash is protected
S2
Not used. Leave set to the factory setting.
Jumper Off
S3
For factory boot flashing only. Leave set to the factory setting.
Jumper Off
Jumper On
Reset
Jumper Off
Normal function
S4
Configures the input voltage of the DC analog tachometer.
Refer to
for configuration.
90V
S9
Configures the input signal of Analog Input 1 (terminals 1 and 2):
On
Off Position
0 - 20 mA / 4 - 20 mA
On Position
0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 71 [Anlg In1 Config].
S10
Configures the input signal of Analog Input 2 (terminal 3 and 4):
On
Off Position
0 - 20 mA / 4 - 20 mA
On Position
0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 76 [Anlg In2 Config].
S11
Configures the input signal of Analog Input 3 (terminals 5 and 6):
On
Off Position
0 - 20 mA / 4 - 20 mA
On Position
0 - 10V / ±10V
Note: The input signal type must also be programmed accordingly
using Par 81 [Anlg In3 Config].
S12
Not used. Leave set to the factory setting.
Off
S14
Field current resistors setting, see
.
Important: In addition, the value selected with switch S14 must be
entered in Par 374 [Drv Fld Brdg Cur] in the control
software when the drive is commissioned.
Minimum
field current
rating
based on
drive size.
S15
Configuration of the control circuit board to the appropriate drive size.
Leave set to the factory setting, unless the control board has been
supplied as a spare part. Refer to
Table 1.N on page 1-34
for switch configuration based on drive current
rating code.
Armature
current
based on
drive size.
S18
Not used. Leave set to the factory setting.
Off
S20
Monitoring of the Z channel of the Digital Encoder on connector XE2: On
Off Position
Z-channel monitored
On Position
Z-channel not monitored
S21
Encoder power supply voltage and input selection:
Note: When control power is supplied to the drive, the appropriate
LED lights to indicate the selection of the switch.
12-15 V
ENC_5
+5 V encoder (+2.5 - 5.4V input range)
ENC_12
+12-15 V encoder (+5.4V - 15.2V input range)
➊
➋
➌
➍
➎
➏
➐
➑
➒