PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
1-36
Installation and Wiring
Figure 1.32 I/O Terminal Block Locations
Table 1.Q I/O Terminal Block 1 Designations
Table 1.R I/O Terminal Block 2 Designations
Terminal Block 1
Terminal Block 3
Terminal Block 4
Terminal Block 2
No. Signal
Description
Factory Default Config. Parameter
1
Analog Input 1 (+)
Isolated
(1)
, bipolar, differential
±
10V / 0-20mA or 4-20mA.
Important: 0-20mA or 4-20mA operation
requires that switch S9, S10, and S11 on
the Control board be in the “Off” position.
Drive damage may occur if the switch is not
in the correct position based on the type of
input signal. Refer to
.
Max
±
10V, Max 0.25mA.
1 “Speed Ref A”
70 [Anlg In1 Sel]
2
Analog Input 1 (–)
3
Analog Input 2 (+)
0 “Off”
75 [Anlg In2 Sel]
4
Analog Input 2 (–)
5
Analog Input 3 (+)
0 “Off”
80 [Anlg In3 Sel]
6
Analog Input 3 (–)
7
+10V Pot Reference
2-5k ohm load. Max
±
10V, 10mA.
–
–
8
–10V Pot Reference
9
Pot Common
For (+) and (–) 10V pot references.
–
–
10
PE ground
PE ground to drive chassis.
–
–
(1)
Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
2
3
4
5
1
7
8
9
10
6
No. Signal
Description
Factory Default Config. Parameter
11
Internal 0V (Gnd)
–
–
12
Digital Input 1
Max +30V, 15V/3.2mA, 24V/5mA,
and 30V/6.4mA.
2 “Stop/CF”
133 [Digital In1 Sel]
13
Digital Input 2
3 “Start”
134 [Digital In2 Sel]
14
Digital Input 3
11 “Jog”
135 [Digital In3 Sel]
15
Digital Input 4
1 “Enable”
(1)
136 [Digital In4 Sel]
16
Digital Input Common
(2)
–
–
17
Not Used
–
–
18
24V Supply Common
Common for the internal power supply.
–
–
19
+24V DC Supply
Drive supplied control input power.
Max. +20-30V, 200mA
(3)
–
–
20
PE ground
PE ground to drive chassis.
–
–
(1)
A digital input (1-8) must be configured for “Enable”.
(2)
When using the in24V DC supply (terminal 19) for digital inputs 1-4, you must connect the digital input common (terminal 16) to the +24V supply common
(terminal 18).
(3)
The total current draw is the sum of encoder power, digital outputs and any other loads connected to terminal 19.
12
1
3
14
15
11
17
1
8
19
20
16