12-22
SP600 AC Drive User Manual
Important:
The drive is shipped from the factory configured for
local OIM (keypad) control. For drive control from the
terminal block inputs, Logic Source Sel (89) must be
set to 0 = Terminal Blk.
Logic Source Sel (89) defines the control source for the following
logic commands (see figure 12.9):
0 = Terminal Blk: Hardware I/O control
1 = Local OIM: Drive-mounted OIM
2 = DPI Port 2: DIN connector DPI port
3 = DPI Port 3: DIN port 2 split with option cable
4 = Reserved
5 = Network: Communications interface
6 = Reserved
7 = All Ports: All control sources active
Important:
Asserting the terminal block input assigned to the OIM
control function overrides parameter 89. You can
switch control from the terminal block to the OIM by
configuring Digital In
x Sel (361-366) to the OIM
control function. This switching will affect logic control
and the speed reference source. Refer to the
parameter 361-366 description for detail.
• Start
• Jog
• Clear Faults
• Direction
• Stop
• Run
Figure 12.9 – Logic Source Sel (89)
Comm
Module
Control
Functions
RUN
START
JOG
DIRECTION
CLEAR
FAULTS
STOP
Logic Source
Sel (89)
Terminal
Block
Local OIM
DPI
Port 3
Network
Remote
OIM
Note: All Ports allows
parallel control of
devices.
DPI
Port 2
Remote
OIM
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......