SP600 AC Drive User Manual
Displays the present frequency reference scaled as a DPI reference
for peer-to-peer communications. The value shown is the value after
the accel/decel ramp but prior to any corrections supplied by slip
comp, PI, etc.
Disables manual requests at the port corresponding to bit number.
Example of manual mode selection source:
If:
• Bit 0 = 0 (Terminal block disabled)
• Bit 1 = 1 (Local OIM enabled)
Then manual mode selection can be activated from the OIM but not
the I/O terminals.
273
Drive Ramp Rslt
Range:
0 to 32767 [1]
Default:
Read Only
Access:
2
Path: Communication>Comm Control
See also:
286
Manual Mask
Range:
See figure 12.44
Default:
See figure 12.44
Access:
2
Path: Communication>Masks & Owners
See also:
Figure 12.44 – Manual Mask (286)
1 1
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0 =Disabled
x =Reserved
Bit #
Factory Default Bit Values
Local OIM
DPI P
or
t 2
Nibble 1
Nibble 2
Nibble 3
Nibble 4
x
x
1
Te
rminal Blk
Reser
ve
d
Netw
or
k
1
1
DPI P
or
t 3
Reser
ve
d
x
x
x
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......