Parameter Descriptions
12-79
Parameter number whose value will be written to a communications
device data table. See figure 12.48.
Selects the type of input signal being used for analog input 1 and 2.
These inputs can be configured as 10 VDC or 4-20 mA inputs. See
scaling parameters 322, 323 (Analog In1) and 325, 326 (Analog
In2).
316
317
Data Out D1 - Link D Word 1
Data Out D2 - Link D Word 2
Range:
0 to 387 [1]
Default:
0 (Disabled)
Access:
2
Path: Communication>Datalinks
See also:
320
Anlg In Config
Range:
See figure 12.49
Default:
See figure 12.49
Access:
0
Path: Inputs & Outputs>Analog Inputs
See also:
322, 323, 325, 326
Figure 12.49 – Anlg In Config (320)
0
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Current
0 =Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
Nibble 1
Nibble 2
Nibble 3
Nibble 4
Analog In1
Bit
Term
0 to 10 VDC
Bit 0 = 0
14, 15
4 to 20 mA
Bit 0 = 1
16, 17
Analog In2
Bit
Term
-10 to +10 VDC
Bit 1 = 0
18, 19
4 to 20 mA
Bit 1 = 1
20, 21
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......