About the Drive
2-15
is running, the transfer of the selected User Set data will not occur
until the drive is stopped, assuming that the Dynamic Mode and the
transfer command are both still active when the drive stops. A
Dynamic Mode command from the user set select parameter (205)
while the drive is running will be immediately rejected.
Typical Setup / Operation:
Step 1.
While in normal mode (Dyn UserSet Cnfg (204) = x0),
enter data into drive and save to User Set using Save to
User Set (199). Repeat for each needed User Set. Check
that Dynamic User Set related Digital Inputs (parameters
361-366) and Datalink Inputs (parameters 300-307) are
programmed the same in each.
Step 2.
Enable Dynamic User Set Mode (Dyn UserSet Cnfg (204)
= x1).
Step 3.
Test restoring each programmed user Set via digital
Inputs or DynUsrSetSel (205). If a Fault or Type 2 Alarm
occurs (Drive Alarm 2 (212) is non-zero), the User Set
causing the error is loaded (see Dyn UserSet Actv (206)
for indication). Return to Normal Mode (Dyn UserSet Cnfg
(204) = x0), correct the Digital Input or Datalink
definition(s), and save to the User Set that was loaded.
Repeat step 2.
Step 4.
Begin normal drive operation. Remember that User Sets
can only be loaded while the drive is stopped.
At power-up, the drive will load operating memory with the values
contained in the active non-volatile storage as part of initialization. If
Dynamic Mode is Enabled, the selected User Set data will be
loaded and processed after drive initialization completes but before
the drive is allowed to become active. If Dynamic Mode is active and
drive power is removed, User Set data will not be saved and any
parameter changes will be lost.
When Dyn UserSet Cnfg (204) is set to Enabled, the drive will
immediately transfer the selected User Set to operating memory as
determined by digital inputs or DynUsrSetSel (205). The drive will
verify that the User Set digital input configuration is identical in all
three sets.
To avoid operational conflict between User Set values, all digital
inputs must be set identically in each user set. If the digital inputs in
each user set are not set identically, a Type 2 alarm is generated.
The condition(s) must be corrected before the drive can become
active.
Load Frm Usr Set (198) and Save to User Set (199) commands are
not permitted in Dynamic Mode because these operations define
data transfer between the active memory and the User Sets.
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......