3-2
SP600 AC Drive User Manual
3.1
General Requirements for the
Installation Site
It is important to properly plan before installing a SP600 AC drive to
ensure that the drive’s environment and operating conditions are
satisfactory.
Note that no devices are to be mounted behind the drive. If
air-cooled devices are mounted near the drive, the hot air exhaust
may raise the ambient temperature level above what is allowed for
safe operation of the drive.
The area behind the drive must be kept clear of all control and
power wiring. Power connections may create electromagnetic fields
that may interfere with control wiring or components when run in
close proximity to the drive.
Read the recommendations in the following sections before
continuing with drive installation.
3.1.1 Verifying Power Module AC Input Ratings
Match Available Power
SP600 drives are suitable for use on a circuit capable of delivering
up to a maximum of 200,000 rms symmetrical amperes and a
maximum of 600 volts (nominal based on drive rating).
!
ATTENTION: To guard against personal injury and/or
equipment damage caused by improper fusing or circuit
breaker selection, use only the recommended line fuses/circuit
breakers specified in section 4.4.
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......