3-6
SP600 AC Drive User Manual
3.1.3 Minimum Mounting Clearances
Be sure there is adequate clearance for air circulation around the
drive. SP600 NEMA 1 drives are rated at 50
°
C. NEMA 4 drives are
rated 40
°
C and can be mounted with minimum side clearance.
For
best air movement, do not mount SP600 AC drives directly above
each other.
Note that no devices are to be mounted behind the drive. This area
must be kept clear of all control and power wiring. See figure 3.3 for
recommended air flow clearances.
Figure 3.3 – Minimum Mounting Clearances
76.2 mm
(3.0 in.)
76.2 mm
(3.0 in.)
76.2 mm
(3.0 in.)
76.2 mm
(3.0 in.)
Clearances apply to all
SP600 Drives
Panel Mount
Flange Mount
NEMA 4x
NEMA 12