7-6
SP600 AC Drive User Manual
Analog Output
Unipolar
0 to +10V Output. Can
Drive a 2k Ohm load
(25 mA short circuit
limit)
Select Source Value:
Param. 342
Adjust Scaling:
Param. 343, 344
2-Wire Control
Non-Reversing
or Reversing with a
Digital Input set to 6
Internal Supply
Disable Digital Input 1:
Param. 361 = 0 “Not Used” or 6
Set Digital Input 2:
Param. 362 = 7 “Run”
2-Wire Control
Reversing
External Supply
Set Digital Input 1:
Param. 361 = 9 “Run Reverse”
Set Digital Input 2:
Param. 362 = 8 “Run Forward”
3-Wire Control
Internal Supply
Use factory default parameter
settings.
3-Wire Control
External Supply
Use factory default parameter
settings.
Digital Output
Form C Relays
Energized in Normal
State.
Select Source:
Param. 380, 384
Table 7.2 – I/O Wiring Examples (Continued)
Input/Output
Connection Example
Required Parameter Settings
+
–
22
23
2
7
8
9
Stop-Run
+24V
Common
1
2
8
Run Fwd
Run Rev
1
2
7
8
9
Stop
Start
+24V
Common
1
2
8
Stop
Start
11
12
13
24
25
26
Power
Source
or
Summary of Contents for Reliance electric 6SP201-015
Page 14: ...1 2 SP600 AC Drive User Manual ...
Page 54: ...Mounting the Drive 3 16 ...
Page 82: ...6 12 SP600 AC Drive User Manual ...
Page 96: ...7 14 SP600 AC Drive User Manual ...
Page 232: ...Parameter Descriptions 12 102 ...
Page 280: ...B 8 SP600 AC Drive User Manual ...
Page 282: ...C 2 SP600 AC Drive User Manual ...
Page 284: ...D 2 SP600 AC Drive User Manual ...
Page 298: ......
Page 299: ......