C.  Low Voltage DC can be used to turn the control 

ON

 and 

OFF.

  Move jumper "J1" from terminal 

7, to terminal 5, (6 remains the same). 

 

Connect a +5 to 30VDC (10mA) signal to 
terminal 12 and the reference (GND) to 
terminal 11 of TB2.  The control will now turn 

ON

 when the DC signal is present at terminals 

11 and 12 of TB2.  This input is optically 
isolated. Refer to Section C of the OFF/ON 
CONTROL GUIDE. 

 

D. AC 

Voltage may be used to turn the control 

ON

 

and 

OFF

.  This requires a 105-250VAC signal, 

with 2mA leakage maximum.  Set up the 
control by moving the jumper "J1" from 
terminal 7, to terminal 5, (6 remains the same). 
 Connect the 105-250VAC Signal to terminal 
12 (L1) and the common (L2) to terminal 10 of 
TB2.  The FC-40 control will now turn 

ON

 

whenever the AC signal is applied to terminals 
10 and 12 of TB2. This input is optically 
isolated.  Refer to Section D of the OFF/ON 
CONTROL GUIDE. 

 

TB-2 terminals 5-7 are transformer isolated from 
the line voltage circuit. 

 

5.  MAIN CONTROL DIAL

 

 

The output power is controlled by the 

MAIN 

CONTROL DIAL

.  A special logarithmic-tapered 

power out curve (non-linear) spreads the power 
broadly across the 

MAIN CONTROL DIAL

 to help 

give maximum "Fine Control" over the output speed 
of the DC motor.   

 

6. SETTING THE SOFT-START

 

 

The start-up of the control output can be adjusted to 
ramp up to the desired output level instead of 
starting abruptly. This keeps parts from falling off 
the tooling of a vibratory feeder when it turns on; it 
can reduce hammering during turn on; it can also 
simulate a paddle switch ON delay.  Adjust the 

SOFT

 Start trimpot clockwise for the gentlest start 

(about a 10-second ramp up to full output).  Turn 
the trimpot fully counter-clockwise for no soft start. 
 
 

7. LINE VOLTAGE COMPENSATION 

 

Fluctuations in the line Voltage can cause a DC 
motor to vary its rate.  The line voltage 
compensation feature adjusts the control's output to 
help compensate for fluctuations in the supply 
voltage. If it becomes necessary to disable this 
feature, remove resistor R4 from the bottom of the 
board with a pair of pliers, twist R4 to snap it off. 

  

  

8.  REMOTE SPEED CONTROL 

 

Remote control of the power signal level can be 
accomplished by the following methods: 

 

A.   0-5VDC Analog input signal may be applied in 

place of the Main Control Dial.   For further 
information, contact  RODIX. 

 

B. 4-20mA signal from a PLC can be used to 

remotely vary the output of the control instead 
of the Main Control Dial.  This feature is 
automatically turned on whenever a 4-20mA 
signal is applied to the control.  To return 
control to the Main Control Dial, remove the 4-
20mA signal by turning it off or use a switch to 
open the circuit.  The 4-20mA input is 
transformer isolated from the power line. 

 

C.   Remote control of the output power level can 

be accomplished by using an optional 

Step 

Up/Down Remote Speed Interface P/N 123-

148

.   

 

WARNING: 

 

Fuses should be replaced with Littelfuse 3AB 

"Fast Acting" type or equivalent of 

manufacturer's original value. 

 

Mounting this control on a vibrating surface will 

void the warranty. 

 

 WARRANTY

 

 

Rodix Control Products are Warranted to be 

free from defects in material and workmanship 

under normal use for a period of two years from 

date of shipment.  

For the full description of the 

warranty, terms, and software license, please 
contact the factory.

 

For assistance installing or operating your Rodix 
Control please call the factory.  Technical help is 
available to answer your questions and Fax any 
needed information.  To return a control for IN or 
OUT of Warranty Service, please ship it prepaid 
to: 

Rodix Inc.,  ATTN: Repair Department

 

If under Warranty, Rodix will repair or replace your 
control at no charge; If out of Warranty, we will 
repair it and you will be billed for the repair charges 
(Time and Material) plus the return freight.  Quotes 
for repairs are available upon request.  A brief note 
describing the symptoms is appreciated by our 
Technicians.

 

 

Feeder Cube

®

 is a registered TM of Rodix Inc. 

 

DIMENSIONS

 

 

 

RODIX, INC.

 

2316 23

rd

 Ave., Rockford, IL  61104 

Toll Free (800) 562-1868

 

E-mail  custserve@rodix.com 

FAX (815) 316-4701 

www.rodix.com 

 

FC-44-DC-PLC Plus 6/2/2011

 

Summary of Contents for FEEDER CUBE FC-40 Plus Series

Page 1: ...AL is turned fully clockwise Turning the MAX Output trimpot clockwise increases the maximum output level 4 REMOTE OFF ON CONTROL Note a Run Jumper has been installed at the factory as shown on the enclosed wiring diagram Remote OFF ON operation of the FC 40 Plus Plus Plus Plus Se Se Se Series ries ries ries Feeder Cube control can be configured to operate in one of the following ways A A low curre...

Page 2: ...essary to disable this feature remove resistor R4 from the bottom of the board with a pair of pliers twist R4 to snap it off 8 REMOTE SPEED CONTROL Remote control of the power signal level can be accomplished by the following methods A 0 5VDC Analog input signal may be applied in place of the Main Control Dial For further information contact RODIX B 4 20mA signal from a PLC can be used to remotely...

Page 3: ...ons for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock input or AUX output The shield drain wire should be tied to the chassis in the Rodix control The drain wire should be kept shorter than 2 Please see the enclosed picture Example of a drain wire termination 2 Never run I O signal wires...

Page 4: ... MODEL RODIX INC FEEDER CUBE FC 44 DC PLC Plus Plus Plus Plus ALL PURPOSE OPEN FRAME MODEL IMPORTANT APPLICATION NOTE MODEL INPUT VAC AMPS OUTPUT FC 44 DC PLC PLUS 120VAC 10A 0 90 or 0 130VDC 6 2 2011 1999 2011 RODIX Inc Customer supplied wiring is shown by dashed lines 7 A 7 12 FC 90 PLUS SERIES AC VOLTAGE INPUT SWITCHING TERM STRIP TB 2 OUTPUT 5 30 VDC INPUT VOLTAGE B L1 7 J1 OFF ON CONTROL 8 FC...

Reviews: