EN
77
Setting deceleration during opening
Setting deceleration during closure
01= barrier decelerates near stop ...
10= barrier decelerates long before reaching the stop.
N.B.:
Available values may be limited by the setting for parameter
$
.
"BreakAway" ACS/BA/60 shatter-proof system enabling (fig. 8)
Connect the shatter-proof system sensor to one of the control inputs on the control unit.
When the shatter-proof system is triggered, the signal switches from N.C. to N.O.
For systems composed of opposing MASTER and SLAVE barriers, disconnect the sensor in the SLAVE barrier
STRICTLY on the ORO input of the SLAVE control unit and set the parameter
.
If NOT connected, all control inputs will have standard function.
Connected on AP input
Connected on CH input
Connected on PP input
Connected on PED input
Connected on ORO input. (For SLAVE barrier: use ONLY for this setting).
SC output operating mode (fig. 9)
By connecting a Relay to the
SC
output, an error alert contact can be achieved at an external control system.
For systems composed of opposing MASTER and SLAVE barriers, perform the connections on the MASTER
control unit. The
SC
output on the SLAVE control unit has standard function set via parameter
$
: the
indicator is off when the barrier is closed. and steadily lit during manoeuvres and when the barrier is open.
STANDARD operation managed by parameter
$
With the indicator lamp connected to the
SC
output and if lit, it indicates that the shatter-proof system sensor
ACS/
BA/60
is in stand-by.
Indicator light off due to an anomaly: sensor alarm.
With the indicator lamp connected to the
SC
output and if lit, it indicates that the barrier is powered by the mains
source or by a charged battery.
Indicator light off due to an anomaly: the battery is exhausted (voltage level set via parameter
).
With the indicator lamp connected to the
SC
output and if lit, it indicates that none of the abnormal situations 1 or
2 occurred.
With the indicator lamp off it indicates that at least one of the abnormal situations 1 or 2 has occurred.
Setting automatic closing time
The timer starts from the barrier open state and continues for the set time. Once the set time is reached, the
barrier closes automatically. The timer count restarts if a photocell is triggered.
pause time settable from 00 to 90 s.
pause time settable from 2 to 9 min.
Enabling of management for opening with automatic re-closure exclusion.
If enabled, the exclusion of automatic re-closure only applies for the command selected via the parameter.
For example: if you set
, automatic re-closure is excluded following an
AP
command, but it is activated
following a
PP
or
PED
command.
NOTE
: The command has open-stop-close or close-stop-open sequence activation function.
NOTE
: The parameter is not visible if par.
$
or
is different than
Disabled.
An
AP
(open) command activates the opening manoeuvre. With the barrier fully open, automatic re-closure is
excluded. Another
AP
(open) command activates the closure manoeuvre.
A
PP
(step mode) command activates the opening manoeuvre. With the barrier fully open, automatic re-closure is
excluded. Another
PP
(step mode) command activates the closure manoeuvre.
A
PED
(partial opening) command activates the partial opening manoeuvre. Automatic re-closure is excluded. Ano-
ther
PED
(partial opening) command activates the closure manoeuvre.
Enable electric block
Disabled.
Normally not powered. The electric lock is powered for 1,5 s at the start of the opening manoeuvre to allow
the barrier to open.
Magnetic "ventouse" electric lock normally powered when the barrier is completely closed. Not powered
when the barrier is moving or completely open
Summary of Contents for CTRL
Page 2: ...2 ...
Page 19: ...19 AGILIK KB MESSA A TERRA GROUNDING SCHEME 16 ...
Page 20: ...20 17 MESSA A TERRA GROUNDING SCHEME BIONIK4 BIONIK4HP BIONIK6 BIONIK8 ...
Page 290: ...290 ...
Page 291: ...291 ...