Safety input and command status (TEST mode)
With no currently active intentional commands, press the TEST button and check the following:
DISPLAY POSSIBLE CAUSE
ACTION BY SOFTWARE
PHYSICAL CORRECTIVE ACTION
U
(rS)
MASTER barrier not moving. STOP con-
tact of MASTER barrier open
(message visible for SLAVE barrier).
-
Check STOP button/contact on MASTER
controller.
Install a STOP button (NC) or jumper the
ST contact with the COM contact of the
MASTER controller.
EU
Detachable boom support system
enabled or not connected or incorrect
connection.
Check the settings of parameter
.
Check the correct system connection to
the control unit.
Safety STOP contact open.
-
Check the STOP button/contact.
Install a STOP button (NC) or jumper the
ST contact with the COM contact.
Release device open.
-
AGILIK-KB-BI/004HP-BI/006-BI/008
Lock by turning the key two complete
turns clockwise.
Check that the microswitch contact is
connected correctly.
BIONIK4
Close the release lock cover and turn
the key.
Check that the microswitch contact is
connected correctly.
Barrier inspection hatch open.
-
Close the barrier inspection hatch.
Check connection to microswitch.
Sensing edge
COS
not connected or in-
correctly connected.
Set the parameter
if not used or
to disable.
If not used jumper contact
COS
with
contact COM.
Photocell
FT
not connected or incorrectly
connected.
Set parameters
and
if not
used or to disable.
If not used jumper contact
FT
with con-
tact COM.
Check connection referring to relative
connection diagram (figures 4-5).
SS
If occurs with no voluntary command, the
contact may be faulty or one of the but-
tons may be incorrectly connected.
-
Check PP - COM contacts and connec-
tions to button.
&+
-
Check CH - COM contacts and connec-
tions to buttons.
DS
-
Check AP - COM contacts and connec-
tions to button.
SH
-
Check PED - COM contacts and connec-
tions to button.
2U
If occurs with no command, the contact
may be faulty or the timer may be incor-
rectly connected.
-
Check contacts ORO - COM.
Do not jumper this contact if not used.
N.B:
press TEST to exit TEST mode.
We recommend troubleshooting safety device and input status errors with “corrective action by software” only.