PROBLEM
ALARM SIGNAL
POSSIBLE CAUSE
CORRECTIVE ACTION
The barrier does
not open or close.
6WRS
flashing
Release device open.
AGILIK-KB-BI/004HP-BI/006-BI/008
: Lock by
turning the key two complete turns clockwise.
BIONIK4
: Close the release lock cover and turn the key.
Open barrier inspection hatch (if
the emergency stop micro-switch
is installed).
Close the inspection hatch correctly and check the
micro-switch connection.
LOCKS connectors incorrectly
connected.
Check the connector connections.
Jumper one of the two LOCKS connectors.
STOP button/contact active for
more than 5 s.
Check connections to STOP button.
For MASTER-SLAVE systems, the
ACS/BA/60
BreakAway system is
active on the MASTER barrier.
Check the BreakAway system and if the alarm event is
solved, re-engage the
ACS/BA/60
system.
(QH
Encoder 1 not connected.
Check connection to encoder.
Replacing the encoder is recommended if the problem
persists.
(QH
Encoder 2 not connected.
Check connection to encoder.
Replacing the encoder is recommended if the problem
persists.
HQ(
Severe encoder 1 malfunction.
Press TEST button. If the error code is displayed again,
switch off the controller unit, wait 5 seconds and switch
on again. Replace the encoder if the problem persists.
HQ(
Severe encoder 2 malfunction.
Press TEST button. If the error code is displayed again,
switch off the controller unit, wait 5 seconds and switch
on again. Replace the encoder if the problem persists.
(QH
(EnE5)
Encoder 1 malfunction.
Press
TEST
button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Operation in battery mode.
Batteries almost flat.
(QH
Encoder 2 malfunction.
Press
TEST
button or perform 3 command requests
in succession. Replace the encoder if the problem
persists.
Operation in battery mode.
Batteries almost flat.
(Q(
Encoder 1 calculation error.
Repeat acquisition procedure.
(Q(
Encoder 2 calculation error.
Repeat acquisition procedure.
Inverter overheat protection trig-
gered.
Function is restored automatically within 2 minutes.
EW/2
(btLO)
Flat batteries.
Wait for mains power to be restored.
No RS485 serial communication
between MASTER barrier and
SLAVE barrier.
Check connection to terminals COM-LNA-LNB.
Check settings of parameter
$
.
Check that battery kit is installed on both MASTER and
SLAVE barriers.
Serial communication interfer-
ence: two MASTER controllers
detected.
Check settings of parameter
$
.
Parameter configuration trans-
fer error between MASTER and
SLAVE.
Check connection to terminals COM-LNA-LNB.
Controller unit models not com-
patible.
Check installation and replace one or both controller
units.
(COM5)
Incompatibility between firmware
versions of controller units.
Check parameter
Q
. Both controllers must have the
same firmware version.
Contact the technical assistance.