background image

00

No safety device in alarm state and no limit switch activated.

27

STOP contact (N.C.) open. 

Jumper the STOP contact. 

25

Sensing edge contact COS1 (N.C.) is open. Check connection. If sensing edge 

is not installed, disable with 

73 00

.

24

Sensing edge contact COS2 (N.C.) is open. Check connection. If sensing edge 

is not installed, disable with 

74 00

.

23

Photocell contact FT1 (N.C.) is open. Check connection. If photocell is not 

installed, disable with 

50 00

.

22

Photocell contact FT2 (N.C.) is open. Check connection. If photocell is not 

installed, disable with 

53 00

.

dATA

Incorrect travel length values / Parameter 

71

 modified: enabling absolute 

encoder (only SMARTY Series).

•  Disconnect from mains power or remove the main fuse (F3) and wait 5 seconds. 

•  Reconnect to mains power or refit the fuse.

•  Press and hold PROG until the message 

ATA

 and 

A

 appear on the display.

Repeat acquisition procedure.

4. Before starting ...

d) Move the gate into the completely CLOSE position.

e) Press TEST button

Possible alarms and safety device messages:

SEE ACQUISITION PROCEDURE

PROG

TEST

+

-

PROG TEST

+

-

PROG

TEST

+

-

a) Select the automation system model installed with the parameter

 

A1

.

b) Select the number of motors installed with the parameter 

70

    This parameter is set for two motors by default. 

c) Position the mechanical stops in both the open and closed positions by tightening them very tightly.

* the parameter 

71 01

 must be set and SMARTY/EMA installed for all applications with the SMARTY REVERSIBLE motor.

1 MOTOR

2 MOTORS

BE20/200/HS

SMARTY 5R5 *

BR20 Series

SMARTY 4HS

BH23/282

BH23/252/HS

BR21 Series

BR21/351/HS

SMARTY 5

BE20/400

SMARTY 7

MONOS4

SMARTY 7R *

BR20/400/R

Summary of Contents for EDGE1

Page 1: ...ulated cable max 10 m 3x4 mm2 max 30 m 1 Photocell Receiver 5x0 5 mm2 double insulated cable max 20 m 2 Photocell Transmitter 3x0 5 mm2 double insulated cable max 20 m 3 Flashing lamp unit 2x1 mm2 double insulated cable max 10 m 4 Antenna RG58 or KX6 50 Ohm cable for external use max 10 m 5 Selector Keypad 3x0 5 mm2 cable max 20 m 1 Typical installation EDGE1 is the range of 36V DC digital control...

Page 2: ... N 0 19 0 26 SEC2 SEC1 1 2 3 4 BATTERY CHARGER BATTERY TRANSFORMER Blu Blue Blu Blue L N Nero Black Nero Black Nero Black Nero Black Blu Blue Blu Blue MOTOR 1 MOTOR 2 FIFTHY 24 F4ES F4S Series 1 2 3 2 3 4 5 TX RX 1 CS STD 1 2 POWER SUPPLY 230 Vac 115 Vac BATTERIES 2 x 12V 4 5Ah 2 Electrical connections 3 Display functions and settings Accessories illustrated are indicative only PROG TEST Back Prog...

Page 3: ...se F3 and wait 5 seconds Reconnect to mains power or refit the fuse Press and hold PROG until the message and appear on the display Repeat acquisition procedure 4 Before starting d Move the gate into the completely CLOSE position e Press TEST button Possible alarms and safety device messages SEE ACQUISITION PROCEDURE PROG TEST PROG TEST PROG TEST a Select the automation system model installed with...

Page 4: ...ment MOTOR2 Deceleration MOTOR 1 during CLOSING Deceleration MOTOR 2 during CLOSING Opening speed Opening speed Closing speed Closing speed Start acceleration MOTOR 2 during opening MOTOR 1 MOTOR 2 6 Setting basic parameters 5 Acquisition procedure 1 Press and hold PROG for 4 seconds 2 APP appears on the display 3 Press PROG 4 AUTO appears on the display 5 MOTOR 1 starts opening at low speed 6 Aft...

Page 5: ... s 3 Hold button A only on the NEW transmitter you want to store 4 The LED flashes 3 s 5 Hold the previously stored transmitter as close as possible to the NEW transmitter 6 Press button A on the OLD transmitter 7 The LED lights for 1 s to confirm that the copy procedure was successful 9 Photocells grounding connection Grounding connection negative terminal COM photocells series F4ES F4S or other ...

Reviews: