background image

 

 

 

Page 

10

 of 

21

 

IP address=192.168.0.80 
Subnet mask=255.255.255.0 
Default gateway=192.168.0.1 
Administrator login: admin 
Administrator password: admin 
UDP port = 3544 
Events recorded in internal flash memory 
Encrypted communication with default password 
 
It is assumed that mentioned above parameters will be changed in particular access control 
installation, specifically IP address and administrator password. These parameters can be modified 

by means of CPR32-NET webpage (see fig 5) opened with web browser e.g. Internet Explorer. 

Note: In order to connect with CPR32-NET in local area network (LAN), the computer must be in 
the same subnet. In case of CPR32-NET with default IP address, the IP address of computer should 
be 192.168.0.xxx. 

 

Fig. 5 CPR32-NET webpage started by means of web browser 

In fig. 5 following configuration options are available: 

Network 

In this window following parameters of CPR32-NET can be modified 

·

 

IP address 

·

 

subnet mask 

·

 

UDP port 

·

 

and other communication parameters 

Passwords 

In this window, administrator password as well as communication password for encrypted 
communication between CPR32-NET and computer with PR Master software can be modified. More 

information on encryption is given in paragraph 4.4.1 Encrypted communication. 

Summary of Contents for CPR32-NET

Page 1: ...Roger Access Control System CPR32 NET network controller User manual Firmware version 1 0 4 or newer Hardware version 1 0 Document version Rev B ...

Page 2: ...EGRA series alarm panels 9 3 5 3 Integration with wireless door locks in SALLIS system 9 3 6 Ethernet port 9 3 7 Installation guidelines 9 4 Configuration 9 4 1 Configuration by means of web browser 9 4 2 Configuration by means of PR Master software 11 4 2 1 New subsystem with CPR32 NET 11 4 2 2 CPR32 NET options 13 4 3 CPR32 NET operation with memory cards 18 4 4 Secure communication with CPR32 N...

Page 3: ... alarm panels of INTEGRA SATEL series time synchronization with NTP server The network controller is equipped with two RS485 ports which are used for communication with access controllers and for integration with INTEGRA or SALLIS systems The communication with computer PR Master software is performed by means of Ethernet port and is secured with AES128 CBC encryption standard Events from access c...

Page 4: ...l Description NC1 REL1 relay output NC IN5 IN5 input line COM1 REL1 relay common terminal IN6 IN6 input line NO1 REL1 relay output NO GND Ground NC2 REL2 relay output NC IN7 IN7 input line COM2 REL2 relay common terminal IN8 IN8 input line NO2 REL2 relay output NO GND Ground BAT Backup battery OUT1 OUT1 output line BAT Backup battery OUT2 OUT2 output line AC 18VAC supply from transformer OUT3 OUT3...

Page 5: ...ation bus controllers IN2 IN2 input line CLK RACS Clock Data comm bus GND Ground DTA RACS Clock Data comm bus IN3 IN3 input line GND Ground IN4 IN4 input line A2 RS485 2 communication bus integrations GND Ground B2 RS485 2 communication bus integrations ...

Page 6: ...Page 6 of 21 Fig 2 Typical connection diagram of CPR32 NET ...

Page 7: ...quently flashing light data memory error frequently flashing ligth RTC error Fig 3 LED indicators on CPR32 NET board 3 3 Power supply Basically CPR32 NET is designed for power supply from 230VAC 18VAC transformer with minimal power output 20VA but it can also be supplied with 12VDC or 24VDC The connection of power supply is shown in fig 4 If CPR32 NET network controller is supplied with 18VAC or 2...

Page 8: ... COM contacts are shorted In case of power outage both outputs remain in the off state 3 4 3 General purpose outputs Six transistor outputs OUT1 OUT6 are available in CPR32 NET network controller All these lines are open collector type i e in the normal off state are pulled to supply plus via 5 6 kΩ resistor and when on they short to supply minus All lines can switch current up to 1A DC while volt...

Page 9: ...8 doors i e 32 doors with PR series single door controllers and 16 doors with SALLIS system door locks More information on integration with wireless door locks of SALLIS system is given in the document Integration of RACS 4 and Sallis wireless lock system Salto User manual 3 6 Ethernet port CPR32 NET is equipped with 10BaseT Ethernet port which is used for communication with computer PR Master sof...

Page 10: ...rer Note In order to connect with CPR32 NET in local area network LAN the computer must be in the same subnet In case of CPR32 NET with default IP address the IP address of computer should be 192 168 0 xxx Fig 5 CPR32 NET webpage started by means of web browser In fig 5 following configuration options are available Network In this window following parameters of CPR32 NET can be modified IP address...

Page 11: ...of PR Master software CPR32 NET acts as central unit with event buffer and Ethernet RS485 communication interface for communication with various devices in RACS 4 system including access controllers 4 2 1 New subsystem with CPR32 NET In order to create new subsystem with CPR32 NET unit and to detect access controllers it is necessary to select the option Networks in the main window of PR Master so...

Page 12: ... connected to RS485 1 bus of CPR32 NET The maximum number of single door controllers connected to CPR32 NET unit equals to 32 units Each controller connected to CPR32 NET must have different address Example of RACS 4 system consisting of two subsystem is shown in fig 8 Multiple CPR32 NET units forming multiple subsystems can operate within single RACS 4 system Each CPR32 NET unit must have differe...

Page 13: ... options by clicking CPR32 NET option in the main window of PR Master software which results in opening of the window shown in fig 9 with summary of CPR32 NET setup and top menu with following options and commands Menu Configuration Settings In the window opened by means of this option the administrator can activate deactivate power supply tests and internal tests of CPR32 NET unit as well as sele...

Page 14: ...arms are cleared in CPR32 NET unit 02 Tamper alarm Constant When the input is activated Tamper alarm is raised and consequently both the output with dedicated function 81 and LED 1 are activated 08 Set all doors to Normal mode Momentary When the input is activated then Normal Door Mode is activated at all controllers doors within subsystem network 09 Set all doors to Unlocked mode Momentary When t...

Page 15: ...ndow opened by means of this option it is possible to assign functions to CPR32 NET outputs CPR32 NET is equipped with 6 transistor outputs and 2 relay outputs Output lines can be normal or inverted type and they are configured in the same way as output lines of RACS 4 controllers The list of available functions is shown in table 5 Table 5 Output functions No Function Description 00 None Output li...

Page 16: ...error is removed 80 Buffer alarm modulated The output is activated when the event memory buffer is full and remains activated until the buffer is cleared The signal is modulated 1 sec of signal 1 sec of pause 81 Tamper alarm The output is activated for 3 minutes if anti sabotage tamper alarm is raised The alarm is raised when the input with function 02 is activated 82 Power supply alarm The output...

Page 17: ...can be entered manually or selected from the list NTP provides Coordinated Universal Time UTC therefore all time zones and daylight saving times are not included and have to be configured in CPR32 NET e g select UTC 1 00 in the field Time zone If CPR32 NET is connected in LAN then port 123 must be forwarded at router in order to enable communication of CPR32 NET with NTP If several CPR32 NET are i...

Page 18: ...2032 battery Switching between built in flash memory and flash memory card in CPR32 NET can be done by means of the PR Master option which can be accessed in CPR32 NET properties i e PR Master CPR32 NET Configuration Settings Events buffer see fig 10 Fig 10 Events buffer option 4 4 Secure communication with CPR32 NET 4 4 1 Encrypted communication The communication between PR Master software and CP...

Page 19: ...figured by means of CPR32 NET webpage in the menu Networks in the field Dedicated host where IP address of such authorized computer can be entered 4 5 Full memory reset of CPR32 NET Full memory reset of CPR32 NET results in erasing of current settings and restoring of default settings Reset procedure Switch off CPR32 NET power supply Remove connections to CLK and DTA terminals if applicable Connec...

Page 20: ... 1 port 1 Connect CPR32 NET to computer with Roger CLD software by means of RS485 communication interface e g UT 2USB or RUD 1 RS485 1 terminals of CPR32 NET must be connected respectively to RS485 terminals of communication interface 2 Start Roger CLD software see fig 13 3 Select serial port COMx with connected communication interface UT 2USB or RUD 1 4 Select frg firmware file by means of Open F...

Page 21: ...er equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment Weight of the equipment is specified in the document...

Reviews: