background image

MCX2D Operating Manual 

  

12.11.2020 

 

3/13 

 

Backup battery 

MCX2D enables battery charging with 0.3A, 0.6A or 0.9A current up to the level of voltage supplied to the 
expander  (nominal  13.8VDC).  The  current  is  selected  with jumpers  (fig. 2). When  battery  voltage  drops  to 
approximately  10V  then  it  is  disconnected  from  expander.  The  battery  is  reconnected  when  the  13.8V 
supply to expander is restored. In order to ensure battery charging up to 80% level within 24h (according to 
EN 60839 standard) following current settings must be applied: 

  300mA for 7Ah battery 

  600mA for 17Ah battery 

  900mA for 24Ah battery 

RS485 bus 

MCX2D  is  an  addressable  device  connected  to  RS485  communication  bus  of  the  MC16  controller.  At  the 
same time the expander distributes the bus to MCT terminals at each door. The expander can be operated 
with  default  ID=100  address  or  it  can  be  assigned  with  the  address  in  range  of  101-115.  All  devices  on 
RS485 bus of MC16 controller including MCX expanders and MCT terminals must have unique addresses 
in range of 100-115. MCX2D is addressed within low level configuration by means of RogerVDM software or 
manually within memory reset procedure.  
In most cases communication works with any cable type (standard telephone cable, shielded or unshielded 
twisted  pair  etc.)  but  the  recommended  cable  is  unshielded  twisted  pair  (U/UTP  cat.5).  Shielded  cables 
should be limited to installations subject to strong electromagnetic interferences. The RS485 communication 
standard used in the RACS 5 system guarantees proper communication in a distance of up to 1200 meters 
as well as high resistance to interferences. 

Note: Do not use more than single pair in UTP cable for RS485 communication bus. 

LED indicators 

Expanders are equipped with LED indicators which are used to signal integral functions. According to further 
mentioned  procedures, the service mode  is started by  placing jumper on  MEM  contacts and restarting the 
expander. 
 

Table 1. LED indicators 

Indicator 

Colour 

Integral functions 

ACL 

Red 

In  normal  mode  the  LED  indicates  backup  power  supply  from  battery 
instead of PSU. 

RUN  

Red 

Single pulse every 4 sec. : normal mode 

Quick pulsing: service mode 

Slow pulsing (0.5s/0.5s): No communication with controller 

Very slow pulsing (1s/1s): Configuration memory error 

 

In case of Memory reset this LED is used for manual addressing. 

TXD 

Red 

LED indicates data transmission to controller  

RXD 

Green 

LED indicates data receiving from controller 

VDR, TML, 
VOUT, AUX 

Green 

LED indicates voltage at particular output. 

LCK 

Red 

LED is on when corresponding LCK output is switched on. 

 

Inputs 

Expander  offers  DC  and  DR  parametric  inputs  of  NO,  NC,  3EOL/DW/NO  and  3EOL/DW/NC  type.  Input 
types and electric parameters such as response time and parametric resistors are defined  within  low level 

Summary of Contents for MCX2D

Page 1: ...Roger Access Control System MCX2D Operating Manual Product version 1 0 Firmware version 1 1 14 or newer Document version Rev H ...

Page 2: ...ic EOL inputs 4 transistor outputs 6 power supply outputs Backup battery charging RS485 interface Removable screw terminals Power supply The expander requires 13 8VDC power supply and it is recommended to apply PS2D power supply unit for that purpose Due to relatively high current between expander and PSU all connections should be made using possibly short cables with adequate cross sections PSxD ...

Page 3: ... recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong electromagnetic interferences The RS485 communication standard used in the RACS 5 system guarantees proper communication in a distance of up to 1200 meters as well as high resistance to interferences Note Do not use more than single pair in UTP cable for RS485 communicatio...

Page 4: ... is caused by CA contacts closing NC input can be in normal or in triggered state In normal state CA contacts are closed Input triggering is caused by CA contacts opening 3EOL DW NO input 3EOL DW NC input 3EOL DW NO input is operated in such way that CA contacts closing is interpreted as triggering of the first input while CB closing is interpreted as triggering of the second input In VISO softwar...

Page 5: ...cated to supply door lock alarm signalling device and other door related devices The terminal VDR is protected with 1 0A electronic fuse The terminal VDR is internally shorted to ground GND Green LED indicator is located at the VDR terminal to signal voltage at the output TML outputs TML power supply output is dedicated to supply readers at door The terminal TML is protected with 0 2A electronic f...

Page 6: ...0 2A output power supply to controller A B RS485 bus to controller Ax Bx RS485 bus to readers TMLx TMLx 13 8VDC 0 2A output power supply to readers VDRx VDRx 13 8VDC 1 0A output power supply to door lock LCKx 15VDC 1A transistor output line door lock BELLx 15VDC 1A transistor output line alarm signalling device DCx Input line door contact DRx Input line exit button x symbol corresponds to the numb...

Page 7: ...16 access controller fig 5 In such scenario the maximal number of expanders operated by MC16 controller depends on its type and it is limited by available range of addresses ID 100 115 on RS485 bus of MC16 controller where all MCX and MCT devices must have unique addresses For example in case of read in out doors it is possible to control max 6 doors in such setup as MC16 PAC 6 3 x MCX2D 12 x MCT ...

Page 8: ...MCX2D Operating Manual 12 11 2020 8 13 Fig 4 Scenario of operation with MC16 PAC 2 KITs Fig 5 Scenario of operation with multiple MCX2D expanders ...

Page 9: ...essing RST button and RUN LED indicator will pulsate 4 Start RogerVDM program select MCX v1 x device v1 x firmware version RS485 communication channel and serial port with RUD 1 interface 5 Click Connect the program will establish connection and will automatically display Configuration tab 6 Enter unoccupied RS485 address in range of 100 115 if necessary and other settings according to requirement...

Page 10: ...RS485 bus Range 4 16 ASCII characters Input types DC1 DR1 DC2 DR2 Parameter defines input type Range 1 NO 2 NC 3 EOL NO 4 EOL NC 5 2EOL NO 6 2EOL NC 7 3EOL NO 8 3EOL NC 9 3EOL DW NO 10 3EOL DW NC Default value for DC is 2 NC Default value for DR is 1 NO Parametric EOL input resistances Tamper Alarm A Alarm B Ohm Parameter defines resistor for parametric EOL inputs Input response times DC1 DR1 DC2 ...

Page 11: ...in moment to select certain address table 5 or press RST button after 16 flashes when ACL and RUN LED indicators are switched on to select default ID 100 address 7 Remove jumper from MEM contacts and restart the device Table 5 RS485 address encoding Number of RUN LED flashes RS485 address Number of RUN LED flashes RS485 address 1 101 9 109 2 102 10 110 3 103 11 111 4 104 12 112 5 105 13 113 6 106 ...

Page 12: ...ttery connected 11 15 VDC no backup battery Current consumption average MCX2D expander 50mA MCX2D expander with maximal load at power outputs and maximal battery charging current 3 5A Battery charging current Configurable 0 3A 0 6A 0 9A Inputs Four DCx DRx parametric inputs Transistor outputs Four LCKx BELLx outputs each with 15V 1A DC max load Power supply outputs Two 13 8VDC 0 2A outputs VOUT AU...

Page 13: ...uct This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of p...

Reviews: