MCX2D Operating Manual
12.11.2020
4/13
configuration (RogerVDM). Input functions are assigned within high level configuration (VISO). Multiple
functions can be assigned to the same input at the same time.
In standard scenario of door control, DC inputs are dedicated to connection of door contacts while DR inputs
are dedicated to connection of exit buttons and they do not require low level configuration as they can be
operated with default settings:
DC inputs: NC type / 50ms response time
DR inputs: NO type / 50ms response time
Table 2. Input types
NO input
NC input
NO input can be in normal or in triggered state. In
normal state C
A
contacts are opened. Input
triggering is caused by C
A
contacts closing.
NC input can be in normal or in triggered state. In
normal state C
A
contacts are closed. Input triggering
is caused by C
A
contacts opening.
3EOL/DW/NO input
3EOL/DW/NC input
3EOL/DW/NO input is operated in such way that C
A
contacts closing is interpreted as triggering of the
first input while C
B
closing is interpreted as
triggering of the second input. In VISO software DW
input type is represented by two independent inputs.
Each can be used for different purpose and
assigned with different function.
3EOL/DW/NC input is operated in such way that C
A
contacts opening is interpreted as triggering of the
first input while C
B
opening is interpreted as
triggering of the second input. In VISO software DW
input type is represented by two independent inputs.
Each can be used for different purpose and
assigned with different function.