MCX2D Operating Manual
12.11.2020
9/13
Fig. 6 Connection diagram for MCX2D expander in MC16-PAC-2-KIT
4.
C
ONFIGURATION
Low level configuration (RogerVDM)
The purpose of low level configuration is to prepare device for operation in RACS 5 system.
Programming procedure with RogerVDM software:
1. Connect the device to RUD-1 interface (fig. 7) and connect the RUD-
1 to computer’s USB port.
2. Place jumper on MEM contacts (fig. 2).
3. Restart the device by pressing RST button and RUN LED indicator will pulsate.
4. Start RogerVDM program, select
MCX v1.x
device,
v1.x
firmware version,
RS485
communication
channel and serial port with RUD-1 interface.
5. Click
Connect,
the program will establish connection and will automatically display
Configuration
tab.
6. Enter unoccupied RS485 address in range of 100-115 (if necessary) and other settings according to
requirements of specific installation.
7. Click
Send to Device
to update the configuration.
8. Optionally make a backup by clicking
Send to File…
and saving settings to file on disk.
9. Remove jumper from MEM contacts and disconnect device from RUD-1 interface.