RFT1000 in RACS 5 User Manual.doc
2017-10-05
7/13
Fig. 5 Proper placing of finger on optical scanner
4.
C
ONFIGURATION
4.1 Low level configuration (RogerVDM)
4.1.1 Configuration of communication parameters
RFT communication parameters which concerns Ethernet network and RS485 bus are configured
with RogerVDM software. Factory default settings are as follows:
IP address = 192.168.0.70
Subnet mask = 255.255.255.0
Port = 13544
Communication is encrypted with default (empty) password
Connection and configuration procedure
1.
Connect the reader to computer by means of Ethernet port.
2.
Configure your computer’s network parameters according to RFT1000 default settings. The IP
address of the computer must be in the same subnet i.e. 192.168.0.xxx.
3.
Install and start RogerVDM software.
4.
In the opened window (fig.6) select
RFT1000 v1.0
device, firmware
1.3
and
Ethernet
communication channel.
5.
IP address and port of RFT1000 reader is automatically detected by RogerVDM software if the
reader and PC with RogerVDM are in the same subnet and communication between them is not
blocked.
6.
Select
Connect
button.