XM-2DR Operating Manual.doc
Page
2
of
7
1.
D
ESCRIPTION AND
S
PECIFICATION
XM-2DR can be used as I/O extension module and it offers two NO/NC input lines as well as two
relay outputs with isolated NO/NC contacts. The module is addressable and it can communicate
only with devices, which can use RACS Clock&Data standard, namely RACS 4 controllers.
Optionally, XM-2DR can also operate as standalone device and then its relay outputs can be
activated by means of high/low voltage at corresponding input lines. In standalone mode, the XM-
2DR does not communicate by means of RACS Clock&Data.
Two versions are available i.e. XM-2DR is equipped with plastic enclosure and is dedicated to
installation on DIN 35mm rail, while XM-2DR-BRD is electronic module without any enclosure but it
is accompanied with adapter for installation on DIN 35mm rail.
Table 1. Specification
Parameter
Description
Supply voltage
Nominal 12 VDC, min/max range 10-15VDC
Current consumption
25mA (both relays deactivated)
110mA (both relays activated)
Relay outputs
REL1: 30VDC/1.5A
REL2: 30VDC/5A
Input lines
NO/NC inputs, electrically biased to +12V via 5.6 k
Ω resisto
r,
triggering level ~3V
Distance
Between controller and XM-2DR module: max 150m
Environmental class
(according to EN 50131-1)
Class IV, -25C..+60C, relative humidity: 10 to 95% (no
condensation), indoor conditions
Dimensions (H x W x D)
XM-2DR:
62 x 85 x 73mm; 3.5 units
XM-2DR-BRD: 80 x 54mm
Weight
XM-2DR:
110g
XM-2DR-BRD: 50g
Certificates
CE