Instrument Functions
R&S
®
NGA100
47
User Manual 5601.8919.02 ─ 03
Figure 6-6: Fuse indicator on respective channel
6.6.1
Fuse Delay, Fuse Linking
The fuse delay and fuse linking functions provide the flexibility to handle a fuse tripped
event when it occurs. When a fuse tripped event triggered, the affected channels are
turned off according to the settings configured in the fuse delay and fuse linking.
With fuse delay function, it allows you to ignore the current peaks set above the current
limit that occurs during the time set in the fuse delay. This prevents the fuse to be trig-
gered in case of a capacitive load.
With fuse linking function, it allows you to logically interlink channels with their elec-
tronic fuses. If a fuse trips during operation, all channels interlinked with this channel
are turned off.
See
Chapter 6.6, "Activating Fuse"
on page 46 for more information.
1. Press [Menu] key.
2. Select "Output" > "Fuse" menu item.
The R&S NGA100 displays the "Fuse" dialog. See
.
Figure 6-7: Fuse dialog
3. Set "Fuse Delay" to a desire value.
You can set a value from 0 s to 10 s in a 0.01 s step size.
Activating Fuse