Power Supply NGMO
Operation
4-12
4.00 / 07-2004
A/B06:
Sample Channel
[Current DVM]
This menu items lets you select the source for the NGMO2
analysis functions. When “current” is selected the analysis
functions use the internal current measure circuits for
analysis (ranges 5A or .5A). In “DVM” mode the external
DVM inputs are used for analysis.
A/B07:
Trigger Level
Range: 5A (0.0000-7.0000A)
Lets you set the trigger level in the 5A range (see menu
item A/B01) and the signal analysis functions. Any value
between 0.0000 A (Auto) and 7.0000 A that is a multiple of
200 uA can be selected. An asterisk on the right of line two
of the LCD indicates when the 5A range has been selected
in menu item A/B01.
A/B08:
Trigger Level
Range 0.5A (0.00-500.00A)
Lets you set the trigger level in the 0.5A range (see menu
item A/B01) and the signal analysis functions. Any value
between 0.00 mA (Auto) and 500.00 mA that is multiple of
10 uA can be selected. An asterisk on the right of line two
of the LCD indicates when 0.5A range has been selected
in menu item A/B01.
A/B09:
Trigger L
e
vel
DVM: (-6.000-25.000V)
Lets you set the trigger level for the DVM input (see menu
item A/B06) and the signal analysis functions. Any value
between -6.000 V (Auto) and +25.000 Volts that is a
multiple of 1 mV can be selected. An asterisk on the right
of line two of the LCD indicates when “Sample Channel:
DVM” has been selected in menu item A/B06.
A/B10:
Trigger Timeout
(0-60.000 seconds)
f you are using the analysis mode (sampling mode) this
function specifies the time in seconds the sampling unit
waits for a trigger condition before a timeout message is
generated after turning sampling mode on. Any value from
0.000 seconds (infinite) to 60.000 seconds can be selec-
ted.
Summary of Contents for NGMO1
Page 8: ...Power Supply NGMO Tables 4 Version 4 00 07 2004 ...
Page 14: ...Power Supply NGMO Safety 2 2 4 00 07 2004 ...
Page 51: ...Operation Power Supply NGMO 4 00 07 2004 4 29 Fig 4 7 Status model structure ...
Page 52: ...Power Supply NGMO Operation 4 30 4 00 07 2004 ...
Page 84: ...Power Supply NGMO Ordering Information 6 2 4 00 07 2004 ...