background image

2

In addition to NFPA 72, use the following location
guidelines to optimize performance and reduce the
chance of false alarms from the alarm:

 

Locate ceiling-mounted smoke alarms in the center

       of a room or hallway at least 4 inches from any

walls or partitions.

 

Locate wall-mounted smoke alarms so the top of
the alarm is 4 to 12 inches below the ceiling.

 

Locate in a suitable environment as follows:

 

Temperature between 40ºF (4.4ºC) and 100ºF

(37.8ºC))

 

Humidity between 0 and 95% non-

condensing

 

Locate away from air conditioners, heating
registers and any other ventilation source that may
interfere with smoke entering the alarm.

 

Mount smoke alarms on a firm permanent surface.

 

Locate away from large metallic objects when listed
with a transmitter.

Installing the Alarm

1.

 

If you are using the alarm/base lock, remove the
two knockouts on the mounting base. See Figure 3.

 

2.

 

Slide the battery compartment cover away from the
alarm to unsnap it and lift it off. See Figure 4.

 

3.

 

Follow the write mode procedure as described in
the receiver installation of the operational manual.

 

4.

 

Observing proper polarity, insert two 3V lithium
batteries into the alarm battery compartment and
replace the battery compartment cover.

 

5.

 

Write message will be sent automatically

       10 seconds after installing the batteries.

 

 

6.

 

Remove the red plastic dust cover from the alarm.
The alarm is shipped with a dust cover for
protection on construction sites with dusty
environments.

 

7.

 

Using the two screws and anchors provided,
mount the base

 

8.

 

Attach the alarm  to the mounting base as follows:

 

Line up the raised tab on the lip of the alarm

with the slot on lip of the mounting base. See
figure. 4

 

Insert the smoke alarm into the base and

turn clockwise approximately 15 degrees. It
should snap firmly into place.

Important:

 the alarm cannot be attached to the

mounting base if no batteries are installed.

9.

 

Test the alarm 

(see Smoke Testing the Alarm)

.

Smoke Testing the Smoke Alarm

Smoke alarms should be tested in place annually using
smoke or canned aerosol simulated smoke. Follow the

                                                       

 

 To generate an additional right mode message,

disconnect the batteries for 30 seconds and then
reconnect them.

instructions on the canned smoke or use the following
steps to test the alarm with smoke:

1.

 

Hold a smoldering punk or cotton wick close to
the smoke entry openings.

2.

 

Gently direct the smoke into the alarm for 20
seconds or until an alarm is indicated.

BE SURE TO PROPERLY EXTINGUISH THE
SMOKE SOURCE AFTER TESTING! The alarm
LED should remain on and the alarm will sound a
temporal rhythm until the Test/Silence button is
pressed. The alarm automatically resets when smoke is
no longer present.

Understanding the Test/Silence
Button

The Test/Silence button on the alarm performs three
functions as follows:

Testing

 = Press the Test/Silence button for 2 seconds.

The alarm performs a sounder test and a sensitivity
test.

Silence alarm

 = Press to silence the sounder during

an alarm. After a few minutes, the sounder and alarm
resume if smoke is still present.

Silence trouble chirp

 = Press to silence a trouble

chirp. The trouble chirp resumes after 24 hours if the
trouble condition is not corrected.

Summary of Contents for Nova 30

Page 1: ...for interfacing Alarm Alarm restore Low battery Maintenance alert Visible only Selecting a Location Selecting a suitable location is critical to the operation of smoke alarms This equipment should be...

Page 2: ...nchors provided mount the base 8 Attach the alarm to the mounting base as follows Line up the raised tab on the lip of the alarm with the slot on lip of the mounting base See figure 4 Insert the smoke...

Page 3: ...es until the alarm is serviced Attaching and Removing the Smoke Alarm To remove the smoke alarm from the mounting base grasp the alarm and turn it counterclockwise approximately 15 degrees The smoke a...

Page 4: ...m and discard See Figure 7 5 Blow out or use a soft bristled brush to remove dust and dirt from the smoke chamber base 6 Line the new smoke chamber up with the smoke chamber base and snap down into pl...

Page 5: ...see if undue heat is present If they seem cool brace your foot against the bottom of the door with your hip against the door and one hand against the top edge Open it slightly If a rush of hot air is...

Page 6: ...CH SHALL BE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER No employee or representative of Seller is authorized to change this warranty in any way or grant any other warranty WARNING This product shoul...

Page 7: ...Characteristics Nominal center frequency 433 92MHz 318MHz Supervision Transmission every 65 min A compatible receiver ROKONET S NOVA PROGRAMMABLE RECEIVERS In order to continue improving its product...

Reviews: