Installation Manual
11
NOTES:
For zones defined as EOL, use 2.21 K
Ω
resistors (supplied).
By default all zones are defined as EOL termination.
The Double End Of Line (DOEL) configuration allows a detector tamper switch, if
violated, to register a tamper condition at the panel without the need for a separate
connection to a designated tamper zone.
Only zones 1-6 can be defined as DEOL. Zones 9-14 are not valid in this
configuration.
Double Zone Wiring
Zone doubling is used to connect two separate zones on one input. Use the following
diagram for appropriate connection. The tamper alarm will be the same for both of the
zones.
3.32K
2.21K
5.62K
Tamper
N.C.
Alarm
N.C.
Tamper
N.C.
Alarm
N.C.
Zone No.1
Zone No.9
To Panel
Zone
Input
3.32K
2.21K
5.62K
Tamper
N.C.
Alarm
N.C.
Tamper
N.C.
Alarm
N.C.
Zone No.1
Zone No.9
To Panel
Zone
Input
For double zone wiring use the supplied resistors.
NOTES:
The location of the resistors is crucial. Any change in the resistors' location will adversely affect
the correct zone identification. Zones 1-6 must be applied with the 3.32K
Ω
resistor. Zones 9-14
must be applied with the 2.21 K
Ω
and 5.62 K
Ω
resistors.
Zones 7 and 8 cannot be defined as double zone termination.