Part No 4801-5162 Rev 09-2019
RS-500/600 M Series Doors
Page 29
14.3
Installation of Prewired Switches (Smart Switches)
Cooler Switches are prewired with a CPC quick connect. Prewire Switches have two switch assemblies: an
Outside Cooler Switch with a 6 foot harness and an Inside Cooler Switch with a 3 foot harness. Shown below in
Diagram 14B is switch layout.
1.
Connect Outside Switch to Controller with
CPC connection. Push and turn CPC
connector until it’s
completely locked in place.
2.
Mount Outside Switch in
desired location on cooler
wall.
Note: Cover removed for mounting.
3.
Drill a 1-3/4 inch hole through Cooler
Wall to run Inside Switch out
to connect to Outside Switch.
4.
Route Inside Switch Harness
through hole and connect to
bottom of Outside Switch
with CPC.
5.
Mount Inside Switch in desired
location.
Note: Cover removed for mounting
.
6.
Install Conduit Straps on conduit
as required. Mount a strap close to
CPC connection to prevent tampering.
Insure conduit is run in a way to prevent
moisture from running
into electrical units.
7.
Seal Hole