NEXUS CALL SYSTEM
by Rondish
P13
2.2 Configuring a Repeater Network
If repeaters are needed for the site, start by connecting the ZP-01(M) into the Nexus controller
and configure the network settings (refer to Section 3.5.4). The repeater units installed around
the facility must match the Network ID and Frequency Channel selected for the Master.
To program each ZP-01(S).
1.
Set Network ID
2.
Set High Frequency Wireless Channel
3.
Set Target Address
4.
Set Data Rate
5.
Set Repeater Address
To enter programming on a ZP-01(S), press and hold the T-SW button on back until the Tx/Rx
LED on the front panel flashes and remains on. To enter a digit, use a screwdriver to select a
number using the Address dial, and enter the digit by pressing T-SW. Each time a digit is
entered the ZP-01(S) will beep in acknowledgment.
2.2.1 Network ID
The Network ID setting must be the same for all ZP-01(S) and ZP-01(M) communicating on the
same Network. This prevents receiving unwanted calls from a nearby system, and allows
multiple networks to operate on the same site.
Adjust the “Address” rotary switch to the required Network ID: