14
Ronk Vigilant
®
Owner’s and Installation Manual
ADJUSTMENTS AND SETTINGS
Vigilant
®
Series Adjustments and Settings
!
DANGER
Never adjust settings on the transfer switch
controller while the controller is energized.
Always completely isolate all power sources from
the controller and transfer switch mechanism
before making any adjustments.
The Vigilant
®
series adjustments and settings may be made from
the onboard transfer switch controller. The general settings and
adjustments are as follows. See the controller user manual for
detailed information on adjustments.
Figure 7
12/24 VDC OPERATION
The control board is designed to operate in a 12 OR 24 VDC
system voltage.
In 12VDC system operation, the controller requires that jumpers
be installed in the 12/24VDC jumper location.
In 24VDC system operation, the controller requires that no
jumpers be installed in the 12/24VDC jumper location.
A total of five jumpers need to be installed for 12VDC operation
as illustrated.
Installing jumpers in the 12/24 VDC jumper locations for 24VDC
system operation may damage the control board.
Jumper
installed
for 12VDC
Jumper
Jumper
Jumper
Jumper
Jumper
Jumper
Jumper
Jumper
Jumper not
installed
for 24VDC
Jumper
Jumper
Jumper not
installed
for 24VDC
Jumper
installed
for 12VDC
Relay (RSC)
TDEC
TDES
12/24VDC
Jumper
Location
1
LED Annuciator
Dip Switch
1
ON
2 3 4 5 6 7 8 9
Adjustable
Pots
Figure 8 – 12/24 VDC Operation