MANUAL TRANSFER
Ronk Vigilant
®
Owner’s and Installation Manual
19
600A Manual Transfer
In 600A transfer switches, the manual transfer lever (M) located
on the contactor is used to manually transfer between the utility
and generator position. A separate removable lever handle is used
to transfer the mechanism. See transfer instructions on the switch
mechanism. Never transfer under a load condition. Always remove
the handle from the manual transfer lever location after each transfer.
!
WARNING
Never allow the removable lever handle to come
in contact with live wires or terminals.
Figure 12 – Removable Lever Handle
Up
M
Trip Select
Figure 13 – Manual Transfer Lever Location
To transfer from Utility to Generator position:
1. Push “Trip” using an object such as a screwdriver to open the
utility poles.
2. Set the removable handle on “M” and operate in the UP
direction while pushing “select” with the screwdriver.
To transfer from Generator to Utility position:
1. Push “Trip” using an object such as a screwdriver to open the
generator poles.
2. Set the removable handle on “M” and operate in the UP
direction.
The transfer switch is in the utility position when reference A on
the contactor is set to the ON position and reference B is set to
the OFF position. The transfer switch is in the generator position
when reference A on the contactor is set to the OFF position and
reference B is set to the ON position, as seen in 400A Manual
Transfer on page 18.
The switch should need to be transferred manually only in the
event of a failure within the VTS controls. Please call technical
support if any transfer failures are observed.