Accura 2350-GAS User Guide
Chapter 2 Accura 2350-GAS Operation/Setup
ⓒ
2014 Rootech Inc. All Rights Reserved
Page 17
Setup Mode
Each time the SET button is short pressed, the next setup menu is selected.
ID
Event
Threshold
1
Hysteresis
1
Definite Time1
Remote Control
1.It is not displayed when the event parameter is set to off.
Note
If there is no button operation for 10 seconds in the setup mode, the screen automatically returns to the display
mode. If there is no button operation for 25 seconds in the edit mode, it automatically returns to the display mode.
ID Setup
ID
Description
[d][d]
1
ID of Accura 2350 module
2
Default 255
Setup range: 0 - 39
1. d
→
decimal number
2. Module IDs are divided into three types of IDs as follows. The standby ID 255 is assigned to all Accura 2350
modules as a factory default value.
Accura 2350 ID
ID
Description
Communication ID
ID 0 - 39
ID of the module that enables communication
Conflict ID
Redundant
IDs
There are more than 2 identical IDs. communication
unavailable
Standby ID
ID 255
Module ID for checking connection status, communication
unavailable
Event Setup
When the event parameter is set to on, the event LED is turned off.
Event
oFF[default]
Event detection mode disabled
on
Event detection mode enabled
An Over event
1
occurs when the measured value rises above the
threshold value for event detection and the definite time elapses.
1. An Over event consists of a start event and an end event.