Controller functions
Page 36
RES-403
Version 1
Part 2 of 3: Error messages as of October 2005 (warnings)
NOTE:
The specified error messages are initially output as warnings (actual value output jumps back and forth
between two values, alarm LED blinks, alarm relay de-energized). When the "START" signal is activated, the
warning changes to a fault (actual value output no longer jumps back and forth, see bold italic values, alarm
LED lit continuously, alarm relay energized).
Error
code
Act. val.
output
voltage
[V]
Cause
Action if machine
started for first time
Action if machine
already operated, HS
band not changed
104
5.33
10
Current signal incorrect,
incorrect impulse transformer
specification
Perform
AUTOCAL
,
check transformer specifi-
cation,
fault areas
Fault areas
("loose contact")
105
Voltage signal incorrect,
incorrect impulse transformer
specification
106
Current and voltage signals
incorrect,
incorrect impulse transformer
specification
302
Temperature too low,
calibration not performed,
loose contact,
ambient temp. fluctuates
Perform
AUTOCAL
and / or
fault areas
("loose contact")
303
Temperature too high,
calibration not performed,
loose contact,
ambient temp. fluctuates
211
6.00
10
Data error
Perform
AUTOCAL
Perform
AUTOCAL