Technical data
Seite 54
UPT-6012
Version 2
Analog output
(actual value)
Terminals 17+18
0…10 VDC, I
max
= 5 mA
Equivalent to 0…300 °C or 0…500 °C
Accuracy: ±1% plus 50 mV
Alarm relay
Terminals 12, 13, 14
U
max
= 30 V (DC/AC), I
max
= 0.2 A, changeover contact, potential-free
Power loss
Max. 20 W
Ambient conditions
Max. altitude: 2000 m
Ambient temperature: +5…+45 °C
Max. relative humidity: 80% at temperatures up to +31 °C, decreasing linearly to
50% relative humidity at +45 °C
Degree of protection
IP20
UL file
E464680
Installation
A minimum safety clearance of 20 mm all round
(e.g. from other devices and wiring) must be
allowed when installing the device.
The moving clip required for fastening must be
facing down for mounting on a horizontal top hat
rail.
End holders to mechanically fix the controller must be fitted at both ends for
mounting on a vertical top hat rail.
Weight
Approx. 0.5 kg (incl. connector plug-in parts)
Housing material
Plastic, polycarbonate, UL-94-V0
Connecting cable
Type / cross-sections
Rigid or flexible; 0.2…2.5 mm² (AWG 24…12)
Plug-in connectors
Plug-in connectors:
Tightening torque: 0.5…0.6 Nm
(screwdriver: SZS 0.6x3.5 mm)
If ferrules are used, they must be crimped in accordance
with DIN 46228 and IEC / EN 60947-1.
This is essential to ensure proper electrical contact in the terminals.
!