Device functions
Version 2
RES-5008
Page 51
Part 2 of 3: Error messages (warnings)
NOTE:
The specified error messages are first output as warnings:
• Actual value output changes between two values
• Alarm LED blinks quickly
• Alarm relay is not active
After activation of the START signal, the output occurs as a fault:
• Actual value output does not change any more, see bold italic values
• Alarm LED lights up continuously
• Alarm relay is active
Error no.
Actual
value
output
Voltage
[V]
Cause
Measure during initial
startup
Measure during
machine operation,
heating element
not changed
8
104
5.33
10
Current signal incorrect
Impulse transformer
incorrectly dimensioned
Perform
AUTOCAL,
Check transformer
specification,
Error ranges
Error ranges
(“Loose contact”)
105
Voltage signal incorrect
Impulse transformer
incorrectly dimensioned
Strong harmonic waves
on mains supply
106
Voltage and current signal
incorrect
Impulse transformer
incorrectly dimensioned
302
Temperature too low
Calibration not performed
Loose contact
Ambient temperature
fluctuates
Perform
AUTOCAL
and/or
Error ranges
(“Loose contact”)
303
Temperature too high
Calibration not performed
Loose contact
Ambient temperature
fluctuates
9
211
6.00
10
Data error
Perform
AUTOCAL
Perform
AUTOCAL