Technical data
Version 2
RES-5008
Page 57
13
Technical data
NOTE
Operation of the RESISTRON
®
Temperature Controller RES-5008 outside of these technical
specifications can lead to loss of warranty and can cause defects.
Design
Regulator:Housing for electrical cabinet mounting
Can be snapped on to TS35 top hat rail (35 mm) in accordance
with EN 60715
Basic surface: 90x75 mm; depth: 135 mm (incl. connection
terminals)
Terminal:Housing for panel mounting
Dimensions (W x H): 96 x 48 mm, depth: 55 mm (without plug)
Line voltage
Connected between neutral conductor and an outside conductor:
110 VAC -15%…300 VAC +10%
or
Connected between two outside conductors:
110 VAC -15%…480 VAC +10%
CAUTION
The voltage between outside conductor and earth must not exceed
300 VAC.
Power supply
Symmetrical TN or TTsystem
Overvoltage category III
CAUTION
Operation in voltage-free system (e.g. IT system) only after checking
with ROPEX.
Line frequency
47…63 Hz, automatic frequency adjustment in this range
Current consumption
(Primary current of
the impulse
transformer)
I
max
= 5 A (ED = 100%)
I
max
= 25 A (ED = 20%, cycle duration 1 min)
A booster must be used for higher current power requirements (
Chapter 16)
24 VDC power supply
Terminals 5+7
24 VDC, I
max
= 200 mA
Tolerance: ±10%
SELV or PELV supplied from maximum 300VAC, Cat II
Measurement range
Secondary voltage U
R
: 0.4 ...120 VAC (lower voltages with MOD 01, higher
voltages with a ROPEX series resistor)
Secondary current I
R
: 30…500 A with current transformer PEX-W4/W5 (lower
currents: Secondary cables lead through the current transformer several times,
higher currents with a load resistor)
The dimensioning is made in the ROPEX application report.