Reference Manual
00809-0100-4377, Rev BA
September 2010
Rosemount 752
2-14
Custom Meter
Configuration
To configure parameters 1 – 8, use the configuration parameters below.
The LCD Transducer Block can be configured to sequence eight different
process variables.
The output from blocks in other devices on the segment can be linked to one
of the inputs of the ISEL block and then displayed on the LCD. The LCD
would then be configured to display the Block Tag of the ISEL block and the
input parameter.
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process
variables will be displayed. Select up to eight display parameters.
BLK_TAG_#
(1)
Enter the Block Tag of the function block that contains the parameter to be
displayed. The default function block tags from the factory are:
PID_1200
ISEL_1300
CHAR_1400
ARITH_1500
INTEG_1600
BLK_TYPE_#
(1)
Enter the Block Type of the function block that contains the parameter to be
displayed. This parameter is generally selected via a drop-down menu with a
list of possible function block types. (e.g. ISEL PID, etc.)
PARAM_INDEX_#
(1)
The PARAM_INDEX_# parameter is generally selected via a drop-down
menu with a list of possible parameter names based upon what is available in
the function block type selected. Choose the parameter to be displayed.
CUSTOM_TAG_#
(1)
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be
configured to be displayed with the parameter in place of the block tag. Enter
a tag of up to five characters.
UNITS_TYPE_#
(1)
The UNITS_TYPE_#
parameter is generally selected via a drop-down menu
with three options: AUTO, CUSTOM, or NONE. Select AUTO only when the
parameter to be displayed is pressure, temperature, or percent. For other
parameters, select CUSTOM and be sure to configure the
CUSTOM_UNITS_# parameter. Select NONE if the parameter is to be
displayed without associated units.
CUSTOM_UNITS_#
(1)
Specify custom units to be displayed with the parameter. Enter up to six
characters. To display Custom Units the UNITS_TYPE_# must be set to
CUSTOM.
(1)
_# represents the specified parameter number.
Summary of Contents for 752
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 1 4 ...
Page 26: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 2 16 ...
Page 38: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 A 4 ...
Page 43: ...Reference Manual 00809 0100 4377 Rev BA September 2010 B 5 Rosemount 752 APPROVAL DRAWINGS ...
Page 44: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 B 6 ...
Page 45: ...Reference Manual 00809 0100 4377 Rev BA September 2010 B 7 Rosemount 752 ...
Page 46: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 B 8 ...
Page 47: ...Reference Manual 00809 0100 4377 Rev BA September 2010 B 9 Rosemount 752 ...
Page 48: ...Reference Manual 00809 0100 4377 Rev BA September 2010 Rosemount 752 B 10 ...
Page 59: ......