VLT
®
8000 AQUA
NOTE
It is important that the values set in parameters
102-106
Nameplate data
correspond to the
nameplate data of the motor with respect to
either star coupling Y or delta coupling
.
102 Motor power, P
M,N
M,N
(MOTOR POWER)
Value:
0.25 HP (0.25 KW)
[25]
0.5 HP (0.37 KW)
[37]
0.75 HP (0.55 KW)
[55]
1 HP (0.75 KW)
[75]
1.5 HP (1.10 KW)
[110]
2 HP (1.50 KW)
[150]
3 HP (2.20 KW)
[220]
4 HP (3.00 KW)
[300]
5 HP (4.00 KW)
[400]
7.5 HP (5.50 KW)
[550]
10 HP (7.50 KW)
[750]
15 HP (11.00 KW)
[1100]
20 HP (15.00 KW)
[1500]
25 HP (18.50 KW)
[1850]
30 HP (22.00 KW)
[2200]
40 HP (30.00 KW)
[3000]
50 HP (37.00 KW)
[3700]
60 HP (45.00 KW)
[4500]
75 HP (55.00 KW)
[5500]
100 HP (75.00 KW)
[7500]
125 HP (90.00 KW)
[9000]
150 HP (110.00 KW)
[11000]
200 HP (132.00 KW)
[13200]
250 HP (160.00 KW)
[16000]
300 HP (200.00 KW)
[20000]
350 HP (250.00 KW)
[25000]
400 HP (300.00 KW)
[30000]
450 HP (315.00 KW)
[31500]
500 HP (355.00 KW)
[35500]
600 HP (400.00 KW)
[40000]
✭
Depends on the unit
Function:
This is where to select the kW value P
M,N
that
corresponds to the rated power of the motor.
At the works, a rated kW value P
M,N
has been
selected that depends on the type of unit.
Description of choice:
Select a value that equals the nameplate data on
the motor. There are 4 possible undersizes or 1
oversize in comparison with the factory setting.
Also, alternatively it is possible to set the value of the
motor power infinitely variable value, see the procedure
for
infinetely variable change of numeric data value
.
103 Motor voltage, U
M,N
(MOTOR VOLTAGE)
Value:
200 V
[200]
208 V
[208]
220 V
[220]
230 V
[230]
240 V
[240]
380 V
[380]
400 V
[400]
415 V
[415]
440 V
[440]
460 V
[460]
480 V
[480]
500 V
[500]
550 V
[550]
575 V
[575]
✭
Depends on the unit
Function:
This is where the rated motor voltage U
M,N
is
set for either star Y or delta
.
Description of choice:
Select a value that equals the nameplate data on
the motor, regardless of the line voltage of the
AFD. Furthermore, alternatively it is possible to set
the value of the motor voltage infinitely variably.
Also refer to the procedure for
infinitely variable
change of numeric data value
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
94
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 100 of 208