VLT
®
8000 AQUA
Programming
318 Function after time out
(LIVE ZERO FUNCT.)
Value:
✭
Off (NO FUNCTION)
[0]
Freeze output frequency (FREEZE OUTPUT FREQ.) [1]
Stop (STOP)
[2]
Jog (JOG FREQUENCY)
[3]
Max. output frequency (MAX FREQUENCY)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This is where to select the function to be
activated after the end of the time-out period
(parameter 317
Time out
).
If a time-out function occurs at the same time
as a bus time-out function (parameter 556
Bus
time interval function
), the time-out function in
parameter 318 will be activated.
Description of choice:
The output frequency of the VLT AFD can be:
-
frozen at the present value [1]
-
overruled to stop [2]
-
overruled to jog frequency [3]
-
overruled to max. output frequency [4]
-
overruled to stop with subsequent trip [5].
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
119
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 125 of 208