VLT
®
8000 AQUA
Programming
■
Service functions 600-631
This parameter group contains functions such as
operating data, data log and fault log.
It also has information on the nameplate
data of the AFD.
These service functions are very useful in connection
with operating and fault analysis in an installation.
600-605 Operating data
Value:
Parameter
no.
Description
Operating data:
Display text
Unit
Range
600
Operating hours
(OPERATING HOURS)
Hours
0 - 130,000.0
601
Hours run
(RUNNING HOURS)
Hours
0 - 130,000.0
602
kWh counter
(KWH COUNTER)
kWh
-
603
No. of cut-ins
(POWER UP‘S)
Nos.
0 - 9999
604
No. of overtemps.
(OVER TEMP‘S)
Nos.
0 - 9999
605
No. of overvoltages
(OVER VOLT‘S)
Nos.
0 - 9999
Function:
These parameters can be read out via the
serial communication port, as well as via the
display in the parameters.
Description of choice:
Parameter 600 Operating hours:
Gives the number of hours in which the AFD
has been in operation. The value is saved every
hour and when the power supply to the unit is
cut off. This value cannot be reset.
Parameter 601 Hours run:
Gives the number of hours in which the motor has
been in operation since being reset in parameter 619
Reset of hours-run counter
. The value is saved every
hour and when the power supply to the unit is cut off.
Parameter 602 kWh counter:
Gives the output power of the AFD. The calculation
is based on the mean value in kWh over one
hour. This value can be reset using parameter
618
Reset of kWh counter
.
Parameter 603 No. of cut-ins:
Gives the number of cut-ins of supply
voltage to the AFD.
Parameter 604 No. of overtemps:
Gives the number of overtemperature errors
on the heat-sink of the AFD.
Parameter 605 No. of overvoltages:
Gives the number of overvoltages on the intermediate
circuit voltage of the AFD. The count is only taken
when Alarm 7
Overvoltage
is active.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port