Factory settings
PNU
#
Parameter
description
Factory setting
Range
Changes
during
operation
4-setup Con-
ver-
sion
index
Data
type
201
Output frequency low limit, f
MIN
0.0 Hz
0.0 - f
MAX
Yes
Yes
-1
6
202
Output frequency , f
MAX
60 Hz/
50 Hz
f
MIN
-120 Hz
Yes
Yes
-1
6
203
Reference site
Hand/Auto linked
reference
Yes
Yes
0
5
204
Minimum Ref ence, Ref
MIN
0.000
0.000-par. 100
Yes
Yes
-3
4
205
Maximum Ref ence, Ref
MAX
60 Hz/
50 Hz
par. 100-999.999,999
Yes
Yes
-3
4
206
Ramp-up time
Depends on the unit
1 - 3600
Yes
Yes
0
7
207
Ramp-down time
Depends on the unit
1 - 3600
Yes
Yes
0
7
208
Automatic ramp-up/down
Enable
Yes
Yes
0
5
209
Jog frequency
10.0 Hz
0.0 - par. 100
Yes
Yes
-1
6
210
Reference type
Preset reference/
Sum
Yes
Yes
0
5
211
Preset Reference 1
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
212
Preset Reference 2
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
213
Preset Reference 3
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
214
Preset Reference 4
0.00 %
-100.00 - 100.00 %
Yes
Yes
-2
3
215
Current limit, I
LIM
1.0 x I
VLT
[A]
0,1-1,1 x I
VLT
,[A]
Yes
Yes
-1
6
216
Frequency bypass, bandwidth
0 Hz
0 - 100 Hz
Yes
Yes
0
6
217
Frequency bypass 1
120 Hz
f
MIN
-120 Hz
Yes
Yes
-1
6
218
Frequency bypass 2
120 Hz
f
MIN
-120 Hz
Yes
Yes
-1
6
219
Frequency bypass 3
120 Hz
f
MIN
-120 Hz
Yes
Yes
-1
6
220
Frequency bypass 4
120 Hz
f
MIN
-120 Hz
Yes
Yes
-1
6
221
Warning: Low current, I
LOW
0.0 A
0.0 - par. 222
Yes
Yes
-1
6
222
Warning: Higth current, I
HIGH
I
VLT,MAX
Par. 221 - I
VLT,MAX
Yes
Yes
-1
6
223
Warning: Low frequency f
LOW
0.0 Hz
0.0 - par. 224
Yes
Yes
-1
6
224
Warning: High frequency f
HIGH
120.0 Hz
Par.
223 - par.
202 (f
MAX
)
Yes
Yes
-1
6
225
Warning: Low reference Ref
LOW
-999,999.999
-999,999.999 - par.
226
Yes
Yes
-3
4
226
Warning: Low reference High
HIGH
999,999.999
Par. 225 - 999,999.999
Yes
Yes
-3
4
227
Warning: Low feedback FB
LOW
-999,999.999
-999,999.999 - par.
228
Yes
Yes
-3
4
228
Warning: High feedback FB
HIGH
999,999.999
Par. 227 - 999,999.999
Yes
Yes
-3
4
229
Initial ramp
OFF
000.1-360.0 s
No
Yes
-1
6
230
Fill rate
OFF
000000.001-
999999.999
Yes
Yes
-3
7
231
Filled setpoint
Par. 413
Par. 413 to par. 205
Yes
Yes
-3
4
) Global factory setting different from North American factory setting.
Changes during operation:
"Yes" means that the parameter can be changed,
while the AFD is in operation. "No" means that the
AFD must be stopped before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same parameter can have four different data
values. "No" means that the data value will
be the same in all four setups.
Conversion index:
This number refers to a conversion figure to be
used when writing or reading to or from a VLT
AFD by means of serial communication.
MG.80.A7.22 - VLT is a registered Danfoss trademark