VLT
®
8000 AQUA
■
Ordering numbers, LC filter modules
Line supply 3 x 200 - 240 V
LC filter
LC filter
Rated current
Max. output
Power
for VLT type
enclosure
at 200 V
frequency
loss
Order no.
8006-8008
IP 00
25.0 A
60 Hz
85 W
175Z4600
8011
IP 00
32 A
60 Hz
90 W
175Z4601
8016
IP 00
46 A
60 Hz
110 W
175Z4602
8022
IP 00
61 A
60 Hz
170 W
175Z4603
8027
IP 00
73 A
60 Hz
250 W
175Z4604
8032
IP 00
88 A
60 Hz
320 W
175Z4605
Line supply 3 x 380 - 480
LC filter
LC filter
Rated current
Max. output
Power
for VLT type
enclosure
at 400/480 V
frequency
loss
Order no.
8006-8011
IP 20
16 A / 16 A
120 Hz
175Z0832
8016
IP 00
24 A/ 21.7 A
60 Hz
125 W
175Z4606
8022
IP 00
32 A / 27.9 A
60 Hz
130 W
175Z4607
8027
IP 00
37.5 A / 32 A
60 Hz
140 W
175Z4608
8032
IP 00
44 A / 41.4 A
60 Hz
170 W
175Z4609
8042
IP 00
61 A / 54 A
60 Hz
250 W
175Z4610
8052
IP 00
73 A / 65 A
60 Hz
360 W
175Z4611
8062
IP 00
90 A / 78 A
60 Hz
450 W
175Z4612
8072
IP 20
106 A / 106 A
60 Hz
175Z4701
8102
IP 20
147 A / 130 A
60 Hz
175Z4702
8122
IP 20
177 A / 160 A
60 Hz
175Z4703
8152
IP 20
212 A / 190 A
60 Hz
175Z4704
8202
IP 20
260 A / 240 A
60 Hz
175Z4705
8252
IP 20
315 A / 302 A
60 Hz
175Z4706
8302
IP 20
395 A / 361 A
60 Hz
175Z4707
8352
IP 20
480 A / 443 A
60 Hz
175Z3139
8450
IP 20
600 A / 540 A
60 Hz
175Z3140
8500
IP 20
658 A / 590 A
60 Hz
175Z3141
8600
IP 20
745 A / 678 A
60 Hz
175Z3142
Regarding LC filters for 525 - 600 V, please
contact Danfoss.
NOTE
When using LC filters, the switching frequency
must be 4.5 kHz (see parameter 407).