VLT
®
8000 AQUA
Installation
■
Technical data, line supply 3 x 380 - 480 V
According to international requirements
VLT type 8450
8500
8600
Output current
I
VLT,N
[A] (380-440 V) 600
658
745
I
VLT, MAX
(60 s) [A] (380-440 V) 660
724
820
I
VLT,N
[A] (441-480 V) 540
590
678
I
VLT, MAX
(60 s) [A] (441-480 V) 594
649
746
Output power
S
VLT,N
[kVA] (400 V) 416
456
516
S
VLT,N
[kVA] (480 V) 430
470
540
Typical shaft output (380-440 V) P
VLT,N
[kW]
315
355
400
Typical shaft output (441-480 V) P
VLT,N
[HP]
450
500
600
Max. cable cross-section to motor and DC-bus [mm
2
]
4) 5)
2 x 400
3 x 150
2 x 400
3 x 150
2 x 400
3 x 150
Max. cable cross-section to motor and DC-bus [AWG]
2) 4) 5)
2 x 750 mcm
3 x 350 mcm
2 x 750 mcm
3 x 350 mcm
2 x 750 mcm
3 x 350 mcm
Min. cable cross-section to motor and DC-bus [mm
2
]
4) 5)
70
70
70
Min. cable cross-section to motor and DC-bus [AWG]
2) 4) 5)
3/0
3/0
3/0
I
L,MAX
[A] (380 V) 584
648
734
Max.
input
current (RMS)
I
L,MAX
[A] (480 V) 526
581
668
Max. cable cross-section to power [mm
2
]
4) 5)
2 x 400
3 x 150
2 x 400
3 x 150
2 x 400
3 x 150
Max. cable cross-section to power [AWG]
2) 4) 5)
2 x 750
3 x 350
2 x 750
3 x 350
2 x 750
3 x 350
Min. cable cross-section to power [mm
2
]
4) 5)
70
70
70
Min. cable cross-section to power [AWG]
2) 4) 5)
3/0
3/0
3/0
Max. pre-fuses
(line)
[-]/UL [A]
1 )
700/700
800/800
800/800
Efficiency
3)
0.97
0.97
0.97
Line contactor
[Danfoss type] CI 300EL
-
-
Weight IP 00/
Chassis
[kg/lbs] 515/1136
560/1235
585/1290
Weight IP 20/
NEMA 1
[kg/lbs] 630/1389
675/1488
700/1544
Weight IP 54/
NEMA 12
[kg/lbs] 640/1411
685/1510
710/1566
Power loss at
max. load
[W] 9450
10650
12000
Enclosure
IP 00/Chassis/IP 20/NEMA 1/IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national
and local regulations on min. cable cross-section. Max. cable cross section is the maximum possible cable cross section that
can be fitted on the terminals.
5. Connection stud 2 x M12/3 x M12.
MG.80.A7.22 - VLT is a registered Danfoss trademark
39