VLT
®
8000 AQUA
Installation
■
Mechanical installation
Please pay attention to the requirements
that apply to integration and field mounting
kit, see the below list. The information given
in the list must be observed to avoid serious damage
or injury, especially when installing large units.
The adjustable frequency drive
must
be
installed vertically.
The adjustable frequency drive is cooled by means of
air circulation. For the unit to be able to release its
cooling air, the
minimum
distance over and below the
unit must be as shown in the illustration below.
To protect the unit from overheating, it must be
ensured that the ambient temperature
does not
rise above the max. temperature stated for the
adjustable frequency drive and that the 24-hour
average temperature is not exceeded
. The max.
temperature and 24-hour average can be seen
from the General Technical section.
When installing the adjustable frequency drive on
a non flat surface, i.e. a frame, please consult
the instruction, MN.50.XX.YY.
If the ambient temperature is in the range of 45° C
- 55° C, derating of the adjustable frequency drive
will be required in accordance with the diagram in
the Design Guide. The service life of the adjustable
frequency drive will be reduced if no allowance is
made for the derating for ambient temperature.