VLT
®
8000 AQUA
Programming
Description of choice:
There is a choice of 33 different data values, see
parameter 007
Large display readout.
010 Small display readout 1.3
(SMALL READOUT 3)
Value:
Se parameter 007
Large display readout
✭
Power [kW]
[6]
Function:
See the functional description for parameter 008
Small data readout.
Data option
LCP display text
[29]
cannot be selected with
Small display readout
.
Description of choice:
There is a choice of 33 different data values, see
parameter 007
Large display readout.
011 Unit of local reference
(UNIT OF LOC REF)
Value:
Hz (HZ)
[0]
✭
% of output frequency range (%) (% OF FMAX)
[1]
Function:
This parameter decides the local reference unit.
Description of choice:
Choose the required unit for local reference.
012 Hand start on LCP
(HAND START BTTN)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This parameter allows selection/deselection of the
Hand start key on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the
[HAND START] key will be inactive.
013 OFF/STOP on LCP
(STOP BUTTON)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This parameter allows selection/deselection of the
local stop key on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the
[OFF/ STOP] key will be inactive.
NOTE
If
Disable
is selected, the motor cannot be
stopped by means of the [OFF/STOP] key.
014 Auto start on LCP
(AUTO START BTTN)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This parameter allows selection/deselection of the
auto start key on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the
[AUTO START] key will be inactive.
015 Reset on LCP
(RESET BUTTON)
Value:
Disable (DISABLE)
[0]
✭
Enable (ENABLE)
[1]
Function:
This parameter allows selection/deselection of
the reset key on the control panel.
Description of choice:
If
Disable
[0] is selected in this parameter, the
[RESET] key will be inactive.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
91
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 97 of 208