www.rosscontrols.com 9
3/2 RSe Series Safe Exhaust Double Valves Integration Guide
28
Disconnect sensor cable from sensor B
OFF
OFF
OFF
1 | 2 to 3
None
ON
OFF
Yes
**
29
Attempt to energize solenoids A & B
ON
-
-
-
-
-
-
-
30
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
31
Reconnect sensor cable to sensor B
-
-
-
-
-
-
ON
-
32
Reset the safety control system
-
-
-
-
-
-
-
No
33
Energize solenoids A & B
ON
ON
ON
1 to 2 | 3
Pressure
OFF
OFF
No
34
Disconnect sensor cable from sensor A
-
-
-
-
-
-
-
-
35
De-energize solenoids A & B
OFF
OFF
OFF
1 | 2 to 3
None
-
ON
Yes
*
36
Reconnect sensor cable to sensor A
-
-
-
-
-
ON
-
-
37
Attempt to energize solenoids A & B
ON
-
-
-
-
-
-
-
38
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
39
Reset the safety control system
-
-
-
-
-
-
-
No
40
Energize solenoids A & B
ON
ON
ON
1 to 2 | 3
Pressure
OFF
OFF
No
41
Disconnect sensor cable from sensor B
-
-
-
-
-
-
-
-
42
De-energize solenoids A & B
OFF
OFF
OFF
1 | 2 to 3
None
ON
-
Yes
*
43
Reconnect sensor cable to sensor B
-
-
-
-
-
-
ON
-
44
Attempt to energize solenoids A & B
ON
-
-
-
-
-
-
-
45
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
46
Reset the safety control system
-
-
-
-
-
-
-
No
47
Energize solenoids A & B
ON
ON
ON
1 to 2 | 3
Pressure
OFF
OFF
No
48
Remove supply air from port 1
-
OFF
OFF
1 | 2 to 3
None
ON
ON
Yes
**
49
Resupply air to port 1
-
-
-
-
-
-
-
-
50
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
51
Reset the safety control system
-
-
-
-
-
-
-
No
52
Disconnect sensor cable from sensor A
OFF
OFF
OFF
1 | 2 to 3
None
OFF
ON
Yes
**
53
Attempt to reset the safety control system
-
-
-
-
-
-
-
-
54
Attempt to energize solenoids A & B
ON
-
-
-
-
-
-
-
55
Reconnect the sensor cable to sensor A
-
-
-
-
-
ON
-
-
56
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
57
Reset the safety control system
-
-
-
-
-
-
-
No
58
Energize solenoids A & B
ON
ON
ON
1 to 2 | 3
Pressure
OFF
OFF
-
59
De-energize solenoids A & B
OFF
OFF
OFF
1 | 2 to 3
None
ON
ON
-
60
Disconnect sensor cable from sensor B
OFF
OFF
OFF
1 | 2 to 3
None
ON
OFF
Yes
**
61
Attempt to reset the safety control system
-
-
-
-
-
-
-
-
62
Attempt to energize solenoids A & B
ON
-
-
-
-
-
-
-
63
Reconnect the sensor cable to sensor B
-
-
-
-
-
-
ON
-
64
De-energize solenoids A & B
OFF
-
-
-
-
-
-
-
65
Reset the safety control system
-
-
-
-
-
-
-
No
66
Energize solenoids A & B
ON
ON
ON
1 to 2 | 3
Pressure
OFF
OFF
-
67
De-energize solenoids A & B
OFF
OFF
OFF
1 | 2 to 3
None
ON
ON
-
Step
Action
Actuate Signal
Sol A
Sol B
Port
Conditions
Outlet
Pressure
Sensor Conditions
Fault ?
Pass/Fail
Sol A & Sol B
Port 2
Sensor A Sensor B
(P/F)
*
Fault should be detected within 250 msec.
**
Fault should occur immediately.