12

 

 

ADJUSTMENTS

 

 

Press and release the ADJUSTMENTS button, with intervals shorter than 1 sec. according to the desired program.

 

 

1x 

- BRAKE

 

 

ENC (with encoder)

 

   

Ñ ENC (without encoder)

 

 

Level 1

 

without brake (default)

 

 

Level 1

 

very weak brake for condominium GHT9 and medium for industrial

 

 

2x 

- BRAKE

 

Level 2

 

brake with 30% torque

 

 

Level 2

 

weak brake for condominiums and strong for industrial

 

 

3x 

- BRAKE

 

Level 3

 

brake with 60% torque

 

 

Level 3

 

medium brake for condominium and very strong for industrial 

(default).

 

 

4x 

- BRAKE

 

level 4

 

brake with 100% torque

 

 

level 4

 

strong brake for condominium - not applicable for industrial

 

 

 

 

 

 

 

 

5x 

- Enables the SOFT STOP function (DO NOT ENABLE IN DZI MODEL)

 

 

6x 

- Disables the SOFT STOP function

 

 

7x 

- Enables the PASS AND CLOSE function of the photocell

 

 

8x 

- Disables the PASS AND CLOSE function of the photocell

 

 

9x 

- BOT A works as "open-to-close" (just like on KXH boards), BOT F just stops and closes.

 

 

10x 

- BOT A only to open, and BOT_F only to close after

 releasing 

the contact.

 

 

11x 

- Enables the HALL limit switch sensor

 

 

12x 

- Disables the HALL limit switch sensor, working only the FF, CM and FA terminals of the Reed Switches.

 

 

13x - 

Reset, puts all settings to the original factory state, including route (default). Note: Does not erase controls. 

 

Putting into Operation

 

  

 

GHT line with encoder, to put the system into operation, follow the following 2 steps: 

 

1 - Gate

 

 

Set 

DIP 2

 to 

OFF

, ENC (WITH ENCODER) and 

DIP 3 to

 LV /PS (LIGHT / HEAVY) according to your application and record a Rossi control to the control panel. 

Note: connect the J9 encoder terminal

 

 

2 - Setup

 

 

Press and hold the ADJUSTMENTS button for 5 seconds until the ST led starts to flash and release the button, then the automatic route recognition process starts at a slow speed; must expect a complete 

opening and closing cycle. Check if the brake level meets the application

 

 

NOTE: 

(VERY IMPORTANT - READ):

 

 

1- Until the SETUP step 2 is done, the ST led will flash slowly and the speed will be reduced.

 

 

2 - Make sure that the magnets are positioned " Hall Limit Switch sensor" on the sliding line or the "Reed Switch Limit Switch" on the tilting and pivoting line, properly identified (FF and FA) before starting the 

recognition process of the route; if there is a need to move the magnet or Reed, repeat step 2 Setup.

 

3 - The "Photocell" safety device will be inoperative in step 1 and 2.

 

 

4 - The Tx, pushbutton or ADJUST button commands have priority over the route recognition process. Therefore, if any of these devices is activated during the recognition process, the system will be 

interrupted and the process of step 2 SETUP must be restarted.

 

5 - In step 2, if the gate is not at the limit switch, the plate moves the gate to a limit switch and then performs a complete opening and closing cycle

 

 

6 - If the magnet has to be repositioned, it will be necessary to redo the recognition of the path from step 2 SETUP.

 

 

7 - Parameter adjustments must be made with the gate stopped; after adjustment, perform a complete opening and closing cycle by the remote control to confirm the adjustment value. 

 

 

Automator without encoder, 

 

1 - Gate 

• Check the FF and FA magnets if they are in the correct position, record a Rossi control and adjust the clutch.

 

 

• Set 

DIP 2

 to 

ON

, Ñ ENC (NO ENCODER). To enable soft stop press SET 5X button, 

DIP 3

 between LV /PS (LIGHT / HEAVY) according to your application. 

 

Malfunction Search

 

 

Malfunction

 

Cause

 

Solutions

 

 

 

 

ST led is blinking slowly, the SETUP process was not done.

 

 

Do the ''Getting Started'' process

 

 

Does not increase speed

 

 

 

Gate is above max weight or locked

 

 

Check the weight limit for the drive and movement

 

of the Gate

 

 

 

 

 

 

 

Does not start SETUP

 

 

Encoder off

 

 

Check J9 connector connection and functionality

 

 

Automator makes noise and 

not movement

 

 

Motor connected to wrong voltage

 

 

Enter the voltage according to the motor label

 

 

 

 

Ÿ The starting capacitor is not connected to the CAP 

terminal of the control panel / damaged capacitor 

 

Ÿ Insert starting capacitor according to the voltage and 

power of the motor / replace capacitor 

 

 

 

Does not start SETUP, led FF 

or

 

FA  intermittent blinking

 

 

Magnet polarity is reversed

 

 

Correctly position the FA and FF magnets

 

 

 

 

 

 

 

Wires V and W are reversed

 

 

Reverse the position of the V and W wires

 

 

 

 

 

 

 

 

The gate is outside the route limit

 

 

start the SETUP process with the gate in the middle of the 

route

 

 

 

 

 

 

 

 

 

 

Magnet polarity is reversed

 

 

Correctly position the FA and FF magnets

 

 

Setup does not finish

 

 

 

 

 

 

Wires V and W are reversed

 

 

Reverse the position of the V and W wires

 

 

 

 

 

The remote control, SET or LEARN buttons were

 

triggered before the end of the process.

 

 

Start the SETUP process without pressing the buttons until

 

complete.

 

 

 

 

Automator does not turn on:

 

ST led intermittently blinking 

 

FS function enabled and SIA 30FS photocell not installed

 

correctly

 

• Check Installation of FS mode in item 6 of the manual.

 

 

 

 

 

 

SIA 30FS photocell with busy beam (obstacle)

 

• Unclog the beam and check wiring

 

 

 

 

 

Gate slamming into frame /

 

leaving the limit switch 

 

The position of the limit switch has been changed after 

SETUP

 

 

Check the position of the magnets and carry out the 

process of Putting into Operation

 

 

 

 

 

 

 

 

The acceleration, deceleration, brakes or

 

 

Adjust the brake levels according to the weight

 

 

speeds are high for the application

 

and automator model

 

 

 

 

 

 

Gate closing after

 

pass the car

 

Ÿ PASS AND CLOSE function enabled with photocell installed 

with the pause time at 0 sec. 

 

Disable the function by pressing the adjustment button 8 

times.

 

 

 

 

 

FF and FA led does not light 

and does not

 

STOP the gate

 

 

Hall limit switch, has been disabled in the control unit

 

 

Press the SET button 11x to enable the sensor end of

 

hall sensor

 

 

 

Does not make soft stop

 

 

DIP 2 in ON function without encoder enabled

 

 

Press SET button 5x to enable soft stop

 

 

 

 

Pg.06

 

 

 

 

 

 