AY-B86x0 

 

Anti-Vandal Outdoor Fingerprint Readers 

User Manual 

1.

 

Introduction 

The AY-B86x0 series are biometric fingerprint and RFID card reader 

with a compact design, which is suitable for installing on a door 

frame. The USB power supply and debug make operations simple. 

The reader IP65 certified for outdoor use. 
Using AxTraxNG, you can register and delete users (see the 

AxTraxNG™ Software Installation and User Manual

). Alternatively, you 

can use master cards to register and delete users while in an offline 

state. 
The standard Wiegand output seamlessly connects to the third-party 

access controllers. 
The reader comes in two models: 

 

AY-B8620 – 125 kHz EM RFID card reader 

 

AY-B8650 – 13.56 MHz MIFARE card reader 

Figure 1: AY-B86x0 

2.

 

Installation 

2.1

 

Mounting 

1.

 

Using the back panel as a guide, drill two holes for mounting 

the back plate onto the surface (Figure 2)

Figure 2: Wall Mounting 

 

2.

 

Insert a suitable wall plug into each screw hole. 

3.

 

Drill a 10-mm (7/16”) hole for the cable. 

4.

 

Screw the back plate onto the wall. 

5.

 

Connect the reader to the controller (see Sectio

 

2.2). A linear 

type power supply is recommended. 

6.

 

Attach the reader to the back plate and secure the reader to the 

back plate with the provided security screw and tools. 

2.2

 

Wiring 

To connect the unit as a reader to an access control unit: 

1.

 

Select the appropriate connections according to Table 1. 

Table 1: Wiring the Unit as a Reader to a Control Panel 

Function 

Cable Color 

Description 

Power 

Red 

12 VDC 

Black 

GND 

Tamper Alarm 

Brown 

Tamper 

Orange 

Tamper 

Wiegand 

Output 

Green 

Wiegand DATA0 Output 

White 

Wiegand DATA1 Output 

Blue 

Wiegand switch 

Black 

GND 

Pulse Signal 

Light brown 

RS-485B/GND 

Light Blue 

RS-485A/pulse signal (3.3 V) 

2.

 

Prepare the controller cable by cutting its jacket back about 

3 cm (1¼") and strip the insulation from the wires about 1.3 cm 

(½"). 

3.

 

Splice the reader’s pigtail wires to the corresponding controller 

wires and cover each joint with insulating tape. 

4.

 

Trim and insulate the ends of all unused conductors individually. 

Do not short any unused wires together. 

 

 

The individual wires from the reader are color coded according the 

Wiegand standard. 

 

When using a separate power supply for the reader, this supply 

and that of the controller must have a common ground. 

 

The reader’s cable shield wire should be preferably attached to an 

earth ground, or a signal ground connection at the panel, or the 

power supply end of the cable. This configuration is best for 

shielding the reader cable from external interference. 

 